Profibus Modules User Manual

EO 09-0009

Formula 6: T

QUI

, T

RDY

and min T

SDR

For access monitoring (T

WD

) and Target Rotation Time (T

TR

):

T

WD

> T

TR

Formula 7: T

WD

and T

TR

For the Data_Control_Time the following rule applies:

Data_Control_Time > 6 * T

WD

Formula 8: Data_Control_Time

If the devices used have different values for min T

SDR

then the

greatest of these values is used for all devices.

Min T

SDR

= max (min T

SDR device 1

, min T

SDR device 2

, ..., min T

SDR device

N

)

Formula 9: Min T

SDR

Example: If for device 1 the value for min T

SDR

200, for device 2 the values 75 and for device 3 the value 125,

then the value of 200 must be used for all devices.
The same applies also for the Bus parameters max T

SDR

, T

SL

, T

QUI

, T

SET

and T

TR

.