Horner APG SmartRail HE599THM100 User Manual
Smartrail, Thermocouple input module (type j, k, t, r), Prefer spring-clamps

MAN0938-02-EN
Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
1/3/2011
Page 1 of 1
1
Specifications
Specifications
THM100
Number of Channels
4
Types Supported
J, K, T, R
J
-200 to +1200 °C
K
-200 to +1300 °C
T
-200 to +400 °C
Temperature
Range
R
0 to +1700 °C
Resolution
J,K,T
0.1°C
R
0.5°C
Full-scale
±0.2% full scale @ 25°C
Cold-Junction
±1°C
Accuracy
Temp. Coefficient
±100ppm/°C CJ (0-55°C)
Warm-up Time
15 minutes
Input Impedance
>10MΩ
Isolation
500V (backplane)
Dielectric Withstand
400Vac for 1 min (ch-ch)
Conversion Time
50mS/ch
Backplane Power Consumed
100mA @ 5V
External Power Required
100mA @ 24V (+/-10%)
Standard Terminal Type
Screw Type, Removable 11-posn
Optional Spring-clamp Plug
HE599TRM011
Storage Temp.
-25° to 70° Celsius
Operating Temp.
-0° to 55° Celsius
Relative Humidity
5 to 95% Non-condensing
Dimensions WxHxD
20mm x 90mm x 60mm
0.79” x 3.54” x 2.36”
Weight
63g (2.2 oz.)
CE & UL Compliance
CE, UL & C-UL
2
Wiring – I/O
3
Reported Data & Configuration Data
Data is reported to the OCS in signed integer format, with a single implied decimal place. For a
temperature of +762.4°C, with a data range configured for °C, the reported data value is 7624
decimal. For a temperature of -12.1°F, with a data range configured for °F, the reported data value
is -121 decimal.
The SmartRail THM100 is configured using Cscape (9.1 or later). The following parameters are
configurable for the THM100:
Cscape Configuration Data – Selectable per channel
Parameter
Selections
Enable
Channel Enable
Disable
K
J
T
Thermocouple Type
R
°C
Data Range
°F
4
Installation / safety
a. All applicable codes and standards should be followed in the installation of this product.
b. Shielded, thermocouple extension wiring of the proper type should be used for best
performance.
c. Shields should be terminated at one end only, at the end providing the best noise shunting.
For detailed installation and a handy checklist that covers panel box layout requirements and
minimum clearances, refer to the hardware manual of the controller you are using.
When found on the product, the following symbols specify:
7
Technical Support
Technical Support at the following locations:
North America:
Tel: 317 916-4274
Fax: 317 639-4279
Web:
http://www.heapg.com
Email:
Europe:
Tel: +353-21-4321266
Fax: +353-21-4321826
Web:
http://www.horner-apg.com
Email:
THM100 LED Status Indication
LED
Meaning
ON = Normal Operation
FLASH = I/O Error
RUN
OFF = No Power or I/O Error
OFF = Normal Operation
ALARM
FLASH = Open Circuit Detected
SmartRail
Thermocouple Input Module (Type J, K, T, R)
HE599THM100
0.1°C Resolution, typical
No part of this publication may be reproduced without the prior agreement and written
permission of Horner APG, Inc. Information in this document is subject to change without
notice.
Warning: Remove power from the OCS controller and any peripheral equipment connected
to this local system before adding or replacing this or any module.
Warning: Consult
user documentation.
Warning: Electrical
Shock Hazard.
+
-
24VDC
N.C.
-
+
-
+
-
+
-
+
1
2
3
4
CH
+
_
24VDC @ 100mA
External Power
SHIELD GROUNDED
AT ONE END ONLY
+
_
+
_
+
_
+
_
Prefer Spring-clamps?
Optional Spring-clamp style plugs are
available as economical wiring accessories.
See specification table for part number(s).
Representative 10-position plug shown.