Getting Started

MAN0575-04-EN

PAGE 15 of 97

© Horner APG.This drawing is the property of Horner APG. And shall not be disclosed or reproduced except as specifically authorised.

Profibus Modules User Manual

EO 09-0009

3.3

Configuration of a SmartStack Profibus DP Master to any Profibus DP Slave


The following describes the steps to configure a SmartStack Profibus DP Master to any Profibus DP
Slave:

Action

Menu in the System Configurator

Create a new project

File > New > PROFIBUS

Copy GSD file of the DP Slave, if the Slave is not in the

selection list. Horner module GSD’s loaded by default.

File > Copy GSD

Choose Horner DP Master and provide bus address

Insert > Master

Choose DP Slave and provide bus address

Insert > Slave

Assign the input and output modules (*1)

Mark the Slave (left Mouse click), then
Settings > Slave Configuration

Assign the offset addresses

Assign the DP Slave Parameter data, if the Slave needs

Parameter data

Mark the Slave (left Mouse click), then
Settings > Parameter Data

Set the bus parameter

Mark the Master (left Mouse click), then
Settings > Bus Parameters

Set device assignment if no automatic assignment has

occurred

Mark the Master (left Mouse click), then
Settings > Device Assignment

Save project

File > Save

Download to the Master.

Mark the Master (left Mouse click), then
Online > Download

Download to the Slave (if a Horner DP Slave).

Mark the Slave (left Mouse click), then
Online > Download

Live List

Mark the Master (left Mouse click), then
Online > Live List

Start Debugger

Mark the Master (left Mouse click), then
Online > Start Debug Mode

Device diagnostic

Mark the Slave (left Mouse click), then
Online > Device Diagnostic

Stop Debugger

Online > Stop Debug Mode

Global Diagnostic

Mark the Master (left Mouse click), then
Online > Global State Field

Transfer user data:

Write output, read input

Mark the Master (left Mouse click), then
Online > I/O Monitor

Figure 3.2. Steps for Configuration of a SmartStack Profibus DP Master to any Profibus DP

Slave

Note (*1): The Offset addresses assigned in the Slave configuration are always related to the DP
Master.