3.3
Configuration of a SmartStack Profibus DP Master to any Profibus DP Slave
The following describes the steps to configure a SmartStack Profibus DP Master to any Profibus DP
Slave:
Action
Menu in the System Configurator
•
Create a new project
File > New > PROFIBUS
•
Copy GSD file of the DP Slave, if the Slave is not in the
selection list. Horner module GSD’s loaded by default.
File > Copy GSD
•
Choose Horner DP Master and provide bus address
Insert > Master
•
Choose DP Slave and provide bus address
Insert > Slave
•
Assign the input and output modules (*1)
Mark the Slave (left Mouse click), then
Settings > Slave Configuration
•
Assign the offset addresses
•
Assign the DP Slave Parameter data, if the Slave needs
Parameter data
Mark the Slave (left Mouse click), then
Settings > Parameter Data
•
Set the bus parameter
Mark the Master (left Mouse click), then
Settings > Bus Parameters
•
Set device assignment if no automatic assignment has
occurred
Mark the Master (left Mouse click), then
Settings > Device Assignment
•
Save project
File > Save
•
Download to the Master.
Mark the Master (left Mouse click), then
Online > Download
•
Download to the Slave (if a Horner DP Slave).
Mark the Slave (left Mouse click), then
Online > Download
•
Live List
Mark the Master (left Mouse click), then
Online > Live List
•
Start Debugger
Mark the Master (left Mouse click), then
Online > Start Debug Mode
•
Device diagnostic
Mark the Slave (left Mouse click), then
Online > Device Diagnostic
•
Stop Debugger
Online > Stop Debug Mode
•
Global Diagnostic
Mark the Master (left Mouse click), then
Online > Global State Field
•
Transfer user data:
Write output, read input
Mark the Master (left Mouse click), then
Online > I/O Monitor
Figure 3.2. Steps for Configuration of a SmartStack Profibus DP Master to any Profibus DP
Slave
Note (*1): The Offset addresses assigned in the Slave configuration are always related to the DP
Master.