CH9: Diagnostics
MAN0575-04-EN
PAGE 63 of 97
© Horner APG.This drawing is the property of Horner APG. And shall not be disclosed or reproduced except as specifically authorised.
Profibus Modules User Manual
EO 09-0009
The meaning of Station State 2:
Station-
Status 2
Set by
DP
Meaning
Slave
Deactivated
(Bit 7)
Master
This bit is set by the Master, if the Slave in its parameter set is marked as inactive, so that
it is taken out from the cyclic I/O exchange.
Reserved
(Bit 6)
- -
Sync Mode
(Bit 5)
Slave
This bit is set by the Slave, when it has received the sync control command.
Freeze Mode
(Bit 4)
Slave
This bit is set by the Slave, when is has received the freeze control command.
Watchdog ON
(Bit 3)
Slave
This bit is set by the DP-Slave, when its Watchdog control is active to supervise its
corresponding Master connection.
Slave Device
(Bit 2)
Slave
This bit is always set by the Slave.
Static Diag
(Bit 1)
Slave
The Slave sets this bit to indicate the Master to be not operative because of a general
error. Typically, the DP Slave is not ready for I/O data transfer. In the case of a set static
diagnostic bit, the Master has to collect diagnostic information as long as this bit is active.
On which events or at what time this bit can be set by a Slave device, is not defined in the
norm description and can not be mentioned here.
Parameter Req
used
(Bit 0)
Slave
The Slave sets this bit to force the Master system to do a new parameterisation. It
remains set until the parameterisation is complete. In case of this error, compare the real
ident number with the GSD ident number in this window. This numbers must be the
same
Table 12: PROFIBUS-DP Diagnostic Station state 2
The meaning of Station State 3:
Station-
Status 3
Set by
Meaning
Ext Diag
Overflow
(Bit 7)
Master
Slave
This bit is set, if there is more extended diagnostic information to report to the Master than
can be given to the Master in one diagnostic telegram. The DP-Slave sets this bit for
example if there is more diagnostic channel information than the Slave can hold in its
diagnostic buffer.
Reserved
(Bit 6 to 0)
- -
Table 13: PROFIBUS-DP Diagnostic Stations status 3