Horner APG SmartRail HE599MIX116 User Manual

Smartrail, Prefer spring-clamps

background image

MAN0936-02-EN

Specifications / Installation

__________________________________________________________________________________________________________________________________________________________________
1/3/2011

Page 1 of 1










1

Specifications

Specifications

INPUTS

Number of Channels

2

Input Ranges

4-20mA, 0-20mA, 0-5V, 0-10V

Absolute Max. Inputs

±15V, ±25mA

Resolution

12-Bit (4uA,5uA,1.25mV, 2.5mV

Input Impedance

1MΩ (voltage), 250Ω (current)

Accuracy

< ±0.5%

Conversion Time

1mS/ch

OUTPUTS

Number of Channels

2

Output Ranges

0-10V, 4-20mA, 0-20mA

Absolute Max. Outputs

±15V, ±25mA

Resolution

12-Bit (2.5mV, 4uA, 5uA)

Maximum Load

>2kΩ (voltage), <510Ω (current)

Accuracy

< ±0.5%

Conversion Time

1mS/ch

General Specifications

Isolation

Photocoupler (Input/Power)

Backplane Power Consumed

50mA @ 5V

External Power Required

62mA @ 24V (+/-10%)

Terminal Type

Screw Type, Removable 11-posn

Optional Spring-clamp Plug

HE599TRM011

Storage Temp.

-25° to 70° Celsius

Operating Temp.

-0° to 55° Celsius

Relative Humidity

5 to 95% Non-condensing

Dimensions WxHxD

20mm x 90mm x 60mm

0.79” x 3.54” x 2.36”

Weight

73g (2.6 oz.)

CE & UL Compliance

CE, UL & C-UL


2

Wiring – I/O








3

Configuration DATA


The SmartRail MIX116 features a dip switch on the front of the unit for selecting voltage (0-10V) or
current (4-20mA or 0-20mA) on a per channel basis. In addition to the physical dip switch, Cscape
(9.1 or later) must be used for software configuration as well. The following parameters are
configurable in Cscape for the MIX116:

Cscape Configuration Data – Selectable per channel

Parameter

Selections

4-20mA
0-20mA

0-5V

Input/Output Range

0-10V

Hold Last State
Go to Minimum

Go to Mid-range

Hold Last State (Outputs)

Go to Maximum






4

Installation / safety






a. All applicable codes and standards should be followed in the installation of this product.
b. Shielded, twisted-pair wiring should be used for best performance.
c. Shields should be grounded at one end only, preferably at the end providing the best noise
shunting.
d. Use the following wire type or equivalent: Belden 8441.

For detailed installation and a handy checklist that covers panel box layout requirements and
minimum clearances, refer to the hardware manual of the controller you are using.

When found on the product, the following symbols specify:






7

Technical Support

Technical Support at the following locations:

North America:
Tel: 317 916-4274
Fax: 317 639-4279
Web:

http://www.heapg.com

Email:

[email protected]

Europe:
Tel: +353-21-4321266
Fax: +353-21-4321826
Web:

http://www.horner-apg.com

Email:

[email protected]










MIX116 LED Status Indication

LED 1

LED 2

Meaning (same for both LEDs)
ON = Normal Operation
FLASH = I/O Error

IN OK

OUT OK

OFF = No Power or I/O Error

SmartRail

0-10V, 4-20mA Analog Input/Output Module

HE599MIX116

12-Bit Resolution

No part of this publication may be reproduced without the prior agreement and written
permission of Horner APG, Inc. Information in this document is subject to change without
notice.

Warning: Remove power from the OCS controller and any peripheral equipment connected
to this local system before adding or replacing this or any module.

Warning: Consult
user documentation.

Warning: Electrical
Shock Hazard.

+

-

24VDC

N.C.

-

CH2

+

-

CH1

+

-

CH2

+

-

CH1

+

CH1

CH2

CH1

CH2

OUTPUT

INPUT

INPUT

OUTPUT

V

I

24VDC @ 130mA
External Power

SHIELD GROUNDED
AT ONE END ONLY

+

-

LOOP PWR

+

-

+

-

4-20mA
TRANSMITTER

0-20mA
<510 OHM
LOAD

0-10V
>2k OHM
LOAD

+

-

0-10VDC

+

-

LOAD

+

-

LOAD

Prefer Spring-clamps?

Optional Spring-clamp style plugs are
available as economical wiring accessories.
See specification table for part number(s).
Representative 10-position plug shown.