Horner APG SmartMod HE359DAC107 User Manual
Smartmod analog output module, 1µ a or 1 mv resolution
MAN0838-04-EN
Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
5/11/2009
Page 1 of 2 ECN # 950
1
Specifications
DAC007
DAC107
DAC007
DAC107
Number of
Channels
2
4
Auxiliary
Voltage
12V @ 20mA (4
channels)
Output
Ranges
0-20mA or 0-10V
Terminal
Type
Screw Type,
Removable
Resolution
1
µ
A or 1 mV
Storage
Temp.
-40
°
to 85
°
Celsius
Operating
Temp.
-10
°
to 60
°
Celsius
Load
Resistance
Voltage: >5Kohm
Current: <500ohm
Relative
Humidity
5 to 95% Non-
condensing
Output
Calibration
Voltage: +/-10mV
Current: +/-20uA
Dimensions
WxHxD
17.5mm x 100mm
x 120mm
0.69” x 3.94” x
4.72”
External
Power
Supply
Voltage
18-30Vdc
Weight
150g (6 oz.)
Required
Power
(Steady
State)
30mA @ 24Vdc,
typical
(100mA max)
Communica-
tions
Modbus/RTU
(binary)
RS-485 half duplex
Required
Power
(Inrush)
Negligible
Factory
Default
Communica-
tions
Parameters
38400 baud, N, 8, 1,
no h/s
Default Modbus ID 1
Isolation
2000Vac for 60
seconds
(Input/Power &
Input/Comms)
Supported
Modbus
Commands
(family)
1,2,3,4,5,6,8,15,16
CE & UL
Compliance
See Compliance Table at
http://www.heapg.com/Pages/TechSupport/ProductCert.html
2
Wiring – I/O
SmartMod
Analog Output Module
HE359DAC007 / HE359DAC107
Selectable 0-20mA or 0-10V
1
µ
A or 1 mV Resolution
Dimensions in inches are 0.69”W x 3.95”H x 4.72”D
Note: Number of I/O terminal connections vary from model to model
I/O
RS-485
DC IN
Pin
#
DAC007
DAC107
Pin
#
DAC007
DAC107
1
I
I
9
I
2
AUX
AUX
10
AUX
3
V
V
11
V
4
GNA
GNA
OUT 0
12
GNA
OUT 2
5
I
I
13
I
6
AUX
AUX
14
AUX
7
V
V
15
V
8
GNA
GNA
OUT 1
16
Only Terminals
1 through 8 are
present on the
DAC007 model
GNA
OUT 3
D-
D+
GND
INIT
A
B
C
D
V-
V+
I
J
10-30Vdc
Notes:
Both ends of the RS-485 network should be terminated with a 100ohm, 1/4W, 1% resistor. Many OCS controllers
feature dip switches or jumpers which enable appropriate termination if the OCS is located on a network end.
Wiring RS-485
Wiring DC IN
ACTIVE
LOOP
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
I
AUX
V
GNA
I
AUX
V
GNA
I
AUX
V
GNA
I
AUX
V
GNA
IN
0
IN
1
IN
2
IN
3
PASSIVE
LOOP
VOLTAGE
+
NOTE: EACH
CHANNEL MAY BE
WIRED
INDEPENDENTLY