Horner APG SmartStack I/O HE800PBS600/HEPBS600 User Manual
Page 14
Getting Started
MAN0575-04-EN
PAGE 14 of 97
© Horner APG.This drawing is the property of Horner APG. And shall not be disclosed or reproduced except as specifically authorised.
Profibus Modules User Manual
EO 09-0009
Figure 3.6
The Network Status is a block of registers 64 bits x 3 tables give status’ of each slave station.
Table 1 indicates the the configured state of the corresponding slave.
1 or On means the Slave is configured in the Master
0 or Off means the Slave is not configured in the Master
Table 2 indicates the state of each slave.
1 or On means the Slave and Master are exchanging their I/O data.
0 or Off means the Slave and Master are not exchanging their I/O data.
Table 3 indicates the diagnostic bit of each slave. (Can only be viewed in Hsycon)
1 or On means the latest received slave diagnostic data are available in the
internal diagnostic buffer.
0 or Off means since the last diagnostic buffer read access of the host, no
values were changed in this buffer.