Horner APG SmartStix HE559DQM706 User Manual
Smartstix, Remote i/o for the ocs/rcs family, Smartstix i/o

MAN0896-01
Specifications / Installation
03/02/2009
Page 1 of 3 ECN # 952
1
GENERAL SPECIFICATIONS
General Specifications
Storage
Temperature
-25
°
to 70
°
C
Operating and
Storage
Humidity
5 to 95% Non-
condensing
Operating
Temperature
0
°
to 55
°
C
Pollution
degree
2 or lower
Atmosphere
Free from
corrosive gases
and excessive
dust
Cooling
method
Self-cooling
Vibration
Occasional Vibration
Frequency
Acceleration
Amplitude
Sweep
Count
10
≤
f < 57 Hz
-
0.075 mm
57
≤
f
≤
150 Hz
9.8 m/s
2
{1G}
-
10 times in
each direction
for X,Y,Z
Continuous Vibration
Frequency
Acceleration
Amplitude
Sweep
Count
10
≤
f <
57 Hz
-
0.035 mm
57
≤
f
≤
150 Hz
4.9 m/s
2
{0.5G}
-
10 times in
each direction
for X,Y,Z
Shocks
Maximum shock
acceleration
147 m/s
2
{15G}
Duration Time
11 ms.
Pulse Wave
Half sine wave pulse (3 times in each of X, Y, Z
directions)
Noise Immunity
Square wave impulse
noise
AC: ± 1,500VDC
DC: ± 900VDC
Electrostatic
Discharge
Voltage: 4kV (contact discharge)
Radiated
electromagnetic field
27 – 500MHz, 10V/m
Severity
level
All power
modules
Digital
I/Os
(Ue
≥
24V)
Digital I/Os
(Ue < 24 V)
Analog I/Os
Communicatio
n I/Os
Fast Transient
Burst Noise
Voltage
2 kV
1 kV
0.25 kV
2
DIMENSIONS
a. DQM706
b. DQM606
c. Terminal Strips
3
NETWORK CABLE
For detailed wiring information, refer to the Control Station Hardware Manual. A
handy checklist is provided that covers panel box layout requirements and minimum
clearances. See Section 10 for our web address.
Pin
Description
RED
1
V+
WHT
2
CAN_H
NC
3
No Connection
BLU
4
CAN_L
BLK
5
V-
4
ID SWITCHES
(SETTING CSCAN NETWORK IDs)
CsCAN Network IDs are set using the hexadecimal number system from 01 to FD. The
decimal equivalent is 1-253. Refer to Section 8, which shows the decimal equivalent of
hexadecimal numbers. Set a unique Network ID by inserting a small Phillips screwdriver
into the two identical switches. Note: The CsCAN Baud Rate for SmartStix I/O is fixed at
125KBaud
SmartStix
TM
HE559DQM606/HE559DQM706
Remote I/O for the OCS/RCS Family
16 DC Outputs (24VDC, positive logic, 0.5A) / 32 DC Outputs (24VDC, positive logic, 0.5A)
4.55 [115.6mm]
4.21 [106.9mm]
1.97 [49.9mm]
1.62 [41.1mm]
0.18 [4.6mm]
1.87
0.31
HE559-With Removable
Strip
6.95 [176.5mm]
6.61 [167.9mm]
1.62 [41.1mm]
0.18 [4.6mm]
1.97 [49.9mm]
Close-up of Switches
006DIM001
Use this switch to set
the Low Digit – has
an x1 multiplier.
Use this switch to set the
High Digit –has an x16
multiplier.
I/O Status LEDs
Power and Diagnostic
LEDs
INPUT
S
LO (x1)
HI (x16)
MS
NS
PWR
SmartStix I/O
2
1
4
5
6
7
8
11
3
9
12
13
14
15
16
10
INPUTS
LO (x1)
HI (x16)
MS
NS
PWR
SmartStix I/O
2
1
4
5
6
7
8
11
3
9
12
13
14
15
16
10
Recommended Cable
Thick:
(Max Distance =
500m)
Belden 3082A
Thin:
(Max Distance =
100m)
Belden 3084A