Dwyer UXF2 User Manual
Page 76
- 66 -
4.5.7.2. How to validate the total pulse output
Description
z
Sets the total pulse output for DO1 OUT and/or DO2 OUT function.
+TOTAL PULSE: Forward flow rate total pulse output.
–TOTAL PULSE: Reverse flow rate total pulse output.
Note: Referring to Section 4.5.6.1., set the pulse value, pulse width, etc.
For actual keying, refer to the typical operation indicated below. Set the parameter protection to OFF beforehand
(Section 4.4.1).
Typical operation Set the DO1 output to "+TOTAL PULSE", and the contact to Normally OFF.
Keying order
Description
Indication
ź
Pressed twice to select the OUTPUT SETUP mode.
OUTPUT SETUP
ENT
ź
Pressed to indicate ZERO ADJUST.
ZERO ADJUST
CLEAR
ź
Pressed 5 times to indicate "DO1 OUT".
* Pressing
key again will select "DO2".
DO1 OUT
NOT USED
ENT
ź
Pressed to blink the cursor.
DO1 OUT
NOT USED
ź
Pressed to indicate "+TOTAL PULSE" on 2nd line. Or,
to select "–TOTAL PULSE", press
key again.
DO1 OUT
+TOTAL PULSE
Pressed to register "+TOTAL PULSE".
DO1 OUT
½½ COMPLETE ½½
Ļ
ENT
ź
ź
ź
ź
--- “+TOTAL PULSE” registered.---
STATUS OUT
CONTACT ACTION
ENT
ź
Pressed to indicate "CONTACT ACTION".
CONTACT ACTION
ACTIVE ON
Pressed to register "ACTIVE ON" (normally OFF).
* If it is desired to select Normally ON, press
key.
CONTACT ACTION
½½ COMPLETE ½½
Ļ
ENT
ź
ź
ź
ź
--- "ACTIVE ON" registered.---
STATUS OUT
CONTACT ACTION
ESC
Press
ESC
key twice, and
key 3 times to resume
the measurement mode.
0.000 m/s
0.000 m3/h
BULLETIN F-70