2. SELECTION OF INSTALLATION PLACE
Select an installation place taking into account the following factors from the viewpoint of ease of maintenance and
checkup, instrument life, and reliability.
(1) A place where ambient temperature and humidity are –20 to +50
qC and 90% RH or less for flow
transmitter (UXF2), and –20 to +60
qC and 90% RH or less for detector SX3.
(2) A place not exposed to direct sunshine nor effects of weather.
(3) Sufficient space for daily inspection, wiring, etc.
(4) A location not subject to radiated heat from a heating furnace, etc.
(5) A location not subjected to corrosive atmosphere.
(6) A location not subject to flooding.
(7) A location free from excessive vibration, dust, dirt and moisture.
2.1. Flow transmitter
Secure at least 100 mm of space between the flow
transmitter and nearby wall. Also secure a space for
opening the front cover for maintenance.
Secure a cable wiring space under the enclosure.
O P
E
N
133
100
133
370 min.
min.
Top view of mounting