beautypg.com

Dwyer 641RM User Manual

Dwyer instruments, inc, Series 641rm air velocity transmitter

background image

Series 641RM Air Velocity Transmitter

Specifications - Installation and Operating Instructions

Bulletin E-66-RM

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.

Fax: 219/872-9057

e-mail: [email protected]

The Series 641RM Air Velocity Transmitter uses a heated
mass flow sensor technology. It has 8 user selectable
ranges from 250 FPM to 15000 FPM with corresponding
metric ranges of 1.25 MPS to 75 MPS. The Series 641RM
Air Velocity Transmitter provides an isolated 4-20 mA out-
put proportional to the velocity. With the optional 1/2˝ 4-1/2
digit LED display, the Series 641RM Air Velocity Transmitter
will provide a highly visible local readout of the velocity.

INSTALLATION
Location:
Select a location where the temperature will be
within 32 to 140°F (0 to 60°C) to mount the enclosure. The
transmitter may be located any distance from the receiver
provided that the total loop resistance does not exceed 600
ohms. The probe should be located where conditions are
representative of the overall environment being monitored.
Avoid locations where turbulence, stagnation, or rapidly
fluctuating velocities or temperatures are present as these
conditions may affect the readings. The filter setting may be
used to average velocity readings in turbulent conditions.

Position: The transmitter is not position sensitive and may
be mounted in any orientation.

Probe Orientation: Dots on the probe indicate the direc-
tion of the calibrated airflow. Align these dots toward the
source of the process air.

Airflow: The Series 641RM Air Velocity Transmitter is
intended for use with clean dry air. Particulates in the air
may cause sensor damage. Dust accumulation may impair
the velocity measurement and will require probe cleaning.

SPECIFICATIONS
Service:
Air and compatible, non-combustible gases.
Accuracy:
3% FS Process gas: 32 to 122°F (0 to 50°C).
4% FS Process gas: -40 to 32°F & 122 to 212°F
(-40 to 0°C & 50 to 100°C).
Response Time: Flow: 1.5 seconds to 95% of final value (out-
put filter set to minimum).
Temperature Limits: Process: -40 to 212°F (-40 to 100°C).
Ambient: 32 to 140°F (0 to 60°C).
Pressure Limit: 100 psi (6.89 bar) maximum.
Humidity Limit: Non-Condensing.
Power Requirements:

12–35 VDC, 10–16 VAC.

Output Signal:

4-20 mA, isolated 24V source, 3 or 4-wire

connection.
Output Filter: Selectable 0.5 –15 (seconds).
Loop Resistance: 600 ohms max.
Current Consumption: 300 mA max.
Electrical Connections: Screw terminal.
Mounting Orientation: Unit not position sensitive. Probe must
be aligned with airflow.
Weight: 13.2 oz (374.26 g).
Cable Length: 6 ft (1.82 m).
Probe Length: 12˝ (30.48 cm) standard.
Probe Diameter: 5/16˝ (0.79 cm).

OPTIONAL DISPLAY VERSION:
Display:
4-1/2 digit 1/2˝ Red LED.
Resolution: 1 FPM, 0.01 MPS
(10 FPM @ 10,000 and 15,000 FPM ranges).
Weight: 13.9 oz (394.16 g).

Agency Approvals: CE
The following standards were used for CE approval:
IEC 61000-4-2: 2001
IEC 61000-4-3: 2002
IEC 61000-4-4: 1995
IEC 61000-4-5: 2001
IEC 61000-4-6: 2003
IEC 55011: 1998
IEC 61326: 2002
89/336/EEC EMC Directive

TO READ DISPLAY UNIT MUST BE MOUNTED HORIZONTALLY
AS SHOWN ABOVE. DISPLAY CAN BE TURNED 180° SO CON-
DUIT OPENING CAN BE POSITIONED TO THE RIGHT OR LEFT.

1/2 NPT

4-31/32

[126.21]

Ш5/16

[Ш7.94]

Ш13/64

[Ш5.16]

14-21/64

[53.07]

FOR A STANDARD 12˝ PROBE

1-5/8 [41.28] WITH LED

1-3/32 [27.78] WITHOUT LED

43/64

[17.07]

6 FT

[152.40]

31/64

[12.30]

1-25/32

[45.24]

1-39/64

[40.88]

641-RM bulletin 2/1/05 11:53 AM Page 1