beautypg.com

Dwyer VTT User Manual

Dwyer instruments, inc

background image

Bulletin AV-3-VTT

The Series VTT Hot-Wire Air Velocity and Temperature Transmitter provides
a versatile unit for air velocity and temperature needs. The VTT offers five field-
selectable ranges as well as operating in metric (m/s, °C) or English (fpm, °F)
units. The VTT can measure up to 30 m/s (6000 fpm) and 50°C (122°F). The units
are available with or without an LCD display which alternates between velocity and
temperature. Series VTT can be ordered in duct mount or remote mount
configurations with 4-20 mA or 0-10V output. The VTT is a useful transmitter for
many common HVAC applications.

INSTALLATION
Position:
The Series VTT Hot-wire probe should be oriented perpendicular to the
airflow for best reading. Ensure that the red dot on the airflow probe is facing
against the airflow by removing the screw on the tip of the probe and rotating the
probe tip 1/4, 1/2, or 3/4 of a turn.

Mounting: The Series VTT can be mounted in any orientation, provided that the
airflow probe is oriented correctly to the flow.

Wall Mount Installation:
Mount the ABS plate on the wall (this plate is supplied with the transmitter). Drilling:
Ø 6 mm (with the screws and pins supplied with the transmitter). Insert the
transmitter on the plate (see A on the drawing below) and rotate its housing in
clockwise direction until you hear a “click” which confirms that the transmitter is
correctly installed). For the model with duct mount, an additional drilling of Ø 14
mm must be done before mounting the plate.

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.

Fax: 219/872-9057

e-mail: [email protected]

Specifications - Installation and Operating Instructions

Series VTT Hot-Wire Air Velocity/Temperature Transmitter

SPECIFICATIONS
Service:
Clean air and compatible, non-combustible gases.
Accuracy: Air Velocity: ±3% of reading ±60 fpm (±0.3 m/s); Temperature: ±0.5%
of reading ±0.6°F (±0.4°C).
Temperature Limits: Ambient: 32 to 122°F (0 to 50°C); Storage: 14 to 158°F
(-10 to 70°C).
Power Supply: 24 VAC/VDC (±10%) 3-4 wires.
Current Consumption: 4-20 mA Output: 80 mA maximum; 0-10V Output: 40
mA.
Response Time: Air velocity: 2 seconds to 1/e (63%) of final value;
Temperature: 5 seconds to 1/e (63%) of final value.
Maximum Loop Resistance: 4-20 mA Output: 500 Ω; 0-10V Output: 1 kΩ.
Display: 5 digit; Resolution 1 fpm (0.1 m/s) 1.0°F (0.1°C). Alternates between
velocity and temperature.
Electrical Connection: Screw terminal block.
Cable Length (Remote Probe): 6.56 ft (2 m).
Enclosure Rating: ABS rated NEMA 4X (IP65).
Mounting: Can be mounted in any orientation. Probe must be aligned with
airflow.
Weight: With Display: 0.32 lb (145 g); Without Display: 0.24 lb (110 g).
Agency Approvals: CE.

Airflow: The Series VTT is intended for use with clean, dry air. Particulates in the
air may cause damage to the sensitive airflow probe. Dust accumulation may
impair the velocity measurement and may require cleaning.

Position of the measuring element in the air flow
The probe must be placed perpendicular to the air flow. For duct mount probes,
you can place the probe’s head front to the air flow, and keep the housing straight:
• Locate the red point marked on the probe’s head.
• Remove the screw located on the tip of the probe’s body.
• Rotate the probe’s head by 1/4 turn, 1/2 turn, or 3/4 turn, in order to place the red
spot front to the air flow.
• Replace the screw on the probe’s body.

ABS
plate

73 mm

+

+

50 mm

68 mm

A

A

7 mm

40 mm

+

+

Ø 8 mm

Ø 4,5 mm

1-21/32

[42.00]

1-21/32

[42.00]

33/64 [13.00]

3-15/16 [100.00]

3-17/64

[83.00]

MODELS VTT-X-N-X-X

(SHOWN WITH REMOTE PROBE MOUNTING)

REMOTE PROBE ASSEMBLY

(SHOWN IN 150 MM LENGTH)

5-29/32

[150.00]

SHOWN IN 150 MM LENGTH

MODELS VTT-X-D-X-X

(SHOWN WITH DUCT MOUNT PROBE)

3-15/16

[100.00]

3-17/64

[83.00]

AV-3-VTT:TEMPLATE 6/1/10 1:25 PM Page 1