Dwyer UXF2 User Manual

Page 54

background image

- 44 -

No.

Setting item

Settable range

Initial value

Settable value

21 Display

2nd

line

decimal point
position

00000.000

………………………
(move to desired decimal position)

22

Flow span-1

0.3 to 10 m/s in
terms of flow
velocity

15.0000m

3

/h

[The unit selected at No. 4]

23

Flow span-2

0.3 to 10 m/s in
terms of flow
velocity

0.0000m

3

/h

[The unit selected at No. 4]

24

Hysteresis

0 to 10%

5.00%

%

25

Burnout

4 menus

Hold

Hold, upper limit, lower limit, zero

26

Anal

og output

Burnout timer

0 to 100sec

10sec

sec

27

Total action

3 menus

Start

Start, stop, reset

28 Pulse

value

0.00001 to 9999999

1m

3

[The unit selected at No. 5]

29 Total

pulse

width

5 menus

5msec

5, 10, 50, 100, 200msec

30

Burnout

2 menus

Hold

Hold, count

31

T

o

tal output

Burnout timer

0 to 100sec

10sec

sec

32 DO1

output

type

ż 5 output contents

menus.

ż 3 alarm menus.
ż Flow switch

range 0 to 10 m/s
in terms of flow
velocity.

ż Total switch range

0.000001 to
99999999

NOT USED

…NOT USED
… Flow direction
… Alarm [all, hard, process]
… Flow switches

Upper limit

[ [The unit selected at No. 4]]

Lower limit

[ [The unit selected at No. 4]]

…Total switch

[ [The unit selected at No. 5]]

33

DO1 output action

2 menus

–––

ON, OFF

34 DO2

output

type

ż 5 output contents

menus.

ż 3 alarm menus.
ż Flow switch

range 0 to 10 m/s
in terms of flow
velocity.

ż Total switch range

0.000001 to
99999999

NOT USED

… Unused
… Flow direction
… Alarm [all, hard, process]
… Flow switches

Upper limit

[ [The unit selected at No. 4]]

Lower limit

[ [The unit selected at No. 4]]

… Total switch

[ [The unit selected at No. 5]]

35

DO output action

2 menus

–––

ON, OFF

36

O

u

tp

u

t

co

n

d

it

io

n

s

Span calibration

0 to 200%

100.0%

%

BULLETIN F-70