Setting the low flow rate cutting, Bulletin f-70 – Dwyer UXF2 User Manual

Page 58

background image

- 48 -

Output

Flow rate

Low flow rate cut setting value

4.5.3. Setting the low flow rate cutting

Description
z

The output can be cut when the flow rate is too low.

z

Effective for indication, analog output (4-20 mA) and total
operation.

Settable range: 0 to 5 [m/s] in terms of flow velocity

(factory set at 0.150 [m

3

/h]).

Notes

1. As required, set the low flow rate cut because the flow meter

may read a flow rate when the fluid in the piping is moving
on account of convection, etc. even if the valves are closed.

2. The flow rate unit is as selected by "FLOW UNIT" in

"MEASURE SETUP" (see Section 4.6.2).

For actual keying, refer to the typical operation indicated below. Set the parameter protection to OFF beforehand
(Section 4.4.1).

Typical operation Set the low flow rate cut point to 0.5 [m

3

/h].

Keying order

Description

Indication

ź

Pressed twice to indicate "OUTPUT SETUP".

OUTPUT SETUP

ENT

ź

Pressed to indicate "ZERO ADJUST".

ZERO ADJUST

SET ZERO

ź

Pressed twice to indicate "CUTOFF".

CUTOFF
0.0010 m3/h

ENT

ź

Pressed to blink the cursor.

CUTOFF

0

000.0010 m3/h

ź

Operated to compose "0.5".

CUTOFF
0000.50

0

0 m3/h

Pressed to register it.

CUTOFF

½½ COMPLETE ½½

Ļ

ENT

ź
ź
ź
ź

--- CUTOFF registered.---

CUTOFF
0.500 m3/h

ESC

Press

ESC

key once, and

key 3 times to resume

the measurement mode.

0.000 m/s
0.000 m3/h

BULLETIN F-70