Setting the damping – Dwyer UXF2 User Manual
Page 57
- 47 -
4.5.2. Setting the damping
Description
z
Used for smoothing the variation of measured value.
A time constant is set (response time of about 63%).
Settable range: 0 to 100 sec in 1 sec steps.
Note: In case 0 sec. is set, response time becomes:
• System cycle:
0.2 sec
• Dead time:
less than 0.2 sec
• Time constant:
0.1 sec
For actual keying, refer to the typical operation indicated below. Set the parameter protection to OFF beforehand
(Section 4.4.1).
Typical operation Change the damping from 5 to 20 sec.
Keying order
Description
Indication
ź
Pressed twice to indicate "OUTPUT SETUP".
OUTPUT SETUP
ENT
ź
Pressed to indicate "ZERO ADJUST".
ZERO ADJUST
SET ZERO
ź
Pressed to indicate "DAMPING".
DAMPING
5 sec
ENT
ź
Pressed to blink the cursor.
DAMPING
0
05 sec
ź
Operated to select "20".
DAMPING
02
0
sec
Pressed to register it.
DAMPING
½½ COMPLETE ½½
Ļ
ENT
ź
ź
ź
ź
--- Damping registered.---
DAMPING
20 sec
ESC
Press
ESC
key once, and
key 3 times to resume
the measurement mode.
0.000 m/s
0.000 m3/h
BULLETIN F-70