2.4 Optonal Termnal Wrng

General Precautons to be Taken Whle Wrng the Input/Output Sgnal Wres

WARNING

• To prevent electric shock while wiring, ensure that the power supply source is

turned OFF.

• If a voltage of more than 30 VAC or 60 VDC is to be applied to the output

terminals, use ring-tongue crimp-on lugs with insulation sleeves on all terminals
to prevent the wires from slipping out when the screws become loose.
Furthermore, use double-insulated wires (dielectric strength of 2300 VAC or
more) for the signal wires on which a voltage of more than 30 VAC or 60 VDC is
to be applied. For all other wires, use basic insulated wires (dielectric strength of
1390 VAC). To prevent electric shock, attach the terminal cover after wiring and
make sure not to touch the terminals.

Crimp-on lug with insulation sleeves (for 4-mm screws)

CAUTION

• The optional terminals of this instrument are specific to this instrument. Do

not connect the optional terminals of the µR1000, µR1800 or other models, as
malfunction may result.

• To prevent fire, use signal wires having a temperature rating of 70°C or more.
• If a strong tension is applied to the cable wired to the recorder, the terminals of

the recorder and/or the cable can be damaged. In order to prevent tension from
being applied directly on the terminals, fasten all wiring cables to the rear of the
mounting panel.

Arrangement of the Optonal Termnals

As shown in the figure below, the optional terminal block is located on the rear panel.
The optional terminal block is provided on the recorder when an option that requires
input/output is installed such as the alarm output relay (/A1, /A2, /A3, /A4 or /A5 option),
FAIL/chart end output (/F1 option), remote control function (/R1 option), RS-422A/485
interface (/C3 option)

*

, and Ethernet (10BASE-T) interface (/C7 option)

*

. A terminal cover

is screwed in place on the measuring input terminal block. A label indicating the terminal
arrangement is affixed to the terminal block.

* For details on terminal and connector arrangement and wiring, see the µR10000 /µR20000

Communication Interface User’s Manual (IM 04P01B01-17E).