6.4 Settng Recordng Zones for Each Channel
(Zone Recordng)
This section explains the details of setting the recording zone for each measurement
channel.
Procedure
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Press the
key or
SHIFT +
key to select
Aux and then press the key.
3.
Press the
key or
SHIFT +
key to select
Zone and then press the key.
4.
Set each item and press the key.
Use the
key or
SHIFT +
key to select values.
For the procedure on how to enter values or characters, see section 4.2.
If you press the
ESC key in the middle of the operation, the settings entered up to
then are cancelled, and the display returns to a higher level menu.
5.
When the
Settng complete screen appears, do either of the following:
Press the key to set other channels.
If you are done, press the
ESC key.
6.
Hold down the
MENU
key for 3 seconds to return to Operation mode.
Set the channel range.
Set the leftmost value of the recording
zone.
Set the rightmost value of the recording
zone.
The new setting takes effect.
First channel
Last channel
ESC/?
Set=Aux
Aux=Zone
CH=01-01
Left= 0
Right=180
01-01 Channel
Setting complete
Explanaton
Zone
The recording zone can be set in the following range.
Leftmost position: 0 mm to 175 mm
Rightmost position: 5 mm to 180 mm
Set a larger value for the rightmost position than the leftmost position.
Set at least 5 mm for the zone width.
Note
If the zone is set to a value less than 40 mm, scale printout of periodic printout cannot be
executed.