beautypg.com

Yokogawa µR20000 User Manual

Page 24

background image

IM 04P02B01-01E

For the procedure to set the functions, see section 1.10, “Function Setup Guide.”

1-8

1.3 Alarms

• Delay Hgh Lmt Alarm (T)

An alarm occurs when the measured value remains above the alarm value for a

specified time period (alarm delay period).

• Delay Low Lmt Alarm (t)

An alarm occurs when the measured value remains below the alarm value for a

specified time period (alarm delay period).

Delay Hgh Lmt Alarm Example (T denotes the specfed delay)

Alarm release

Alarm occurrence

T

X1

X2

X3

X4

T1

Measured value

Alarm value

• Alarm does not occur at T1, because the time period is shorter than the specified

alarm delay period (T).

• The measured value exceeds the alarm value at time X2, and the alarm occurs at

time X3 at which the specified alarm delay period elapses (the time when the alarm
occurs is the time at X3).

• The measured value falls below the alarm value at time X4, and the alarm is

released.

Note

• The alarm detection operation is reset when a power failure occurs. The operation restarts

after the power recovers.

• If the alarm value is changed while a delay alarm is occurring, the alarm is released if the

new alarm value does not meet the alarm condition.

Alarm Hysteress

Hysteresis can be specified to the values for activating and releasing the alarm. The
hysteresis applies only to high limit alarm (H) and low limit alarm (L). The hysteresis
width can be set in the range of 0.0% (Off) to 1.0% of the recording span in 0.1 steps.
The setting applies to all high limit alarms and low limit alarms. By default, the hysteresis
width is set to 0.5%.

Alarm

value

Alarm release

Measured value

Alarm occurrence

High limit alarm

Low limit alarm

Measured

value

Alarm release

Hysteresis

(1% or less)

Alarm value

Alarm occurrence

Setting alarms: Section 5.2

Setting the alarm delay function: Sections 7.15 and 6.10
Setting the alarm hysteresis: Section 7.1