Yokogawa µR20000 User Manual

Page 104

background image

5-3

IM 04P02B01-01E

Frequently

Used

Setup

Operat

ons
(Sett

ng

Mode)

1

2

3

4

5

6

7

8

9

10

11

12

App

Index

Lnear Scalng

Select Scale.

Set the channel range.

Select Volt, TC, RTD, or DI.

Select the range type.

Set the left span value.

Set the right span value.

Set the decimal position and left scale

value.

Set the right scale value.

The new setting takes effect.

ESC/?

Set=Range

CH=01-01

Mode=Scale

Type=Volt

Range=2V

Span left= -2.000

Span right= 2.000

Scale left= 0.00

Scale right= 200.00

01-01 Channel

Setting complete

First channel

Last channel

Descrpton

• Scale Left, Scale Rght, and Decmal Poston

Selectable range (mantissa): –20000 to 30000
Example: The value in the range of –100.00 to 350.00 cannot be specified. The

mantissa of scale right is 35000, which exceeds the upper limit of 30000.
Set in the range of –100.0 to 350.0.

Decimal position: XXXXX, XXXX.X, XXX.XX, XX.XXX, X.XXXX
The decimal position is the position specified by scale left.
Example: Change 0.00 to 0.0.
Press the

key to move the cursor to the last digit of 0.00.

Space

Press the key to change the value to 0.0 .

Note

The displayable/printable range of scale values is –19999 to 30000 excluding the decimal.

Setting the unit: Section 5.3

5.1 Settng the Input Range