beautypg.com

Skp (unused channels) – Yokogawa µR20000 User Manual

Page 109

background image

IM 04P02B01-01E

5-8

• Scale Left, Scale Rght, and Decmal Poston

Selectable range (mantissa): –20000 to 30000
Example: The value in the range of –100.00 to 350.00 cannot be specified. The

mantissa of scale right is 35000, which exceeds the upper limit of 30000.
Set in the range of –100.0 to 350.0.

Decimal position: XXXXX, XXXX.X, XXX.XX, XX.XXX, X.XXXX
The decimal position is the position specified by scale left.
Example: Change 0.00 to 0.0.
Press the

key to move the cursor to the last digit of 0.00.

Space

Press the key to change the value to 0.0 .

Make sure that scale left is less than scale right.

• Low-cut and Low-cut Pont

If low-cut is set to On, set the low-cut point.
Selectable range of the low-cut point: 0.0 to 5.0% of the recording span
Values below the low-cut point is set to 0% (scale left value) of the recording span.

Note

• The displayable/printable range of scale values is –19999 to 30000 excluding the decimal.
• If the leftmost value of the scale is set to –20000 (excluding the decimal) and the low-cut

value is set to –20000, the value when the low-cut function is applied is displayed as
“–Over.”

Setting the unit: Section 5.3

Enabling the low-cut function: Section 7.15

Skp (Unused Channels)

Select Skip.

Set the channel range.

The new setting takes effect.

First channel

Last channel

ESC/?

Set=Range

CH=01-01

Mode=Skip

01-01 Channel

Setting complete

Note

Do not use channels set to skip as a reference channel of delta computations or in computing
equations of the computation function (/M1 option).

5.1 Settng the Input Range