1 changing the auxiliary alarm function, Mode), 1 changing the auxiliary alarm function -1 – Yokogawa µR20000 User Manual
Page 138: 1 changng the auxlary alarm functon
7-1
IM 04P02B01-01E
Setup
Operat
ons
for
Chang
ng/Add
ng
Funct
ons
(Bas
c
Sett
ng
Mode)
1
2
3
4
5
6
7
8
9
10
11
12
App
Index
7.1 Changng the Auxlary Alarm Functon
This section explains the details of setting the alarm system items listed below.
• Diagnosis output using the alarm output relay (I01)
• Reflash alarm operation of the alarm output relay (I01 to I03)
• AND/OR operation of alarm output relays
• Energized/De-energized operation of alarm output relays when alarms occur
• Hold/Non-hold operation of alarm output relays
• Hold/Non-hold operation of alarm indications
• The interval of the rate-of-change alarm
• Alarm hysteresis
Basic Setting mode cannot be entered when recording is in progress or when
computation is in progress on models with the computation function (/M1 option).
Procedure
Changng the Settngs
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the
and
keys simultaneously for 3 seconds to enter Basic
Setting mode.
3.
Press the key with
Alarm shown on the screen.
4.
Set each item and press the key.
Use the
key or
SHIFT +
key to select values.
For the procedure on how to enter values or characters, see section 4.2.
If you press the
ESC key in the middle of the operation, the settings entered up to
then are cancelled, and the display returns to a higher level menu.
5.
When the
Settng complete screen appears, do either of the following:
To correct the setting, press the key.
If you are done, press the
ESC key.
Chapter 7
Setup Operatons for Changng/Addng Functons (Basc Settng Mode)