For the procedure to set the functions, see section 1.10, “Function Setup Guide.”
1.3 Alarms
1
2
3
4
5
6
7
8
9
10
11
12
App
Index
AND/OR Operaton of Alarm Output Relays
When multiple alarms are assigned to one alarm output relay, the condition for activating
the alarm output relay can be selected from the following:
• AND: Activated when all assigned alarms are occurring simultaneously.
• OR: Activated when any of the specified alarms is occurring.
Alarm
Channel 01
AND
Channel 02
OR
Alarm output relay
The alarm output relays assigned to AND operation are specified as follows: “I01 (first
relay) to Ixx (where xx is the relay number).”
The default setting is “no AND relay.”
Note
• If the reflash alarm is enabled, I01 to I03 are fixed to OR operation. Specifying AND
produces no effect.
• If diagnosis output is enabled, I01 is set to diagnosis output. Specifying AND produces no
effect.
Energzed/De-energzed Operaton of Alarm Output Relays
You can select whether the alarm output relay is energized or de-energized when an
alarm occurs. If de-energized is selected, the status of the alarm output relay when an
alarm occurs is the same as the status that results when the recorder is turned OFF
(including power failures). The setting applies to all alarm output relays.
The default setting is energized.
NO
Energize
De-energize
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
NO
C
NC
When power is
turned OFF
NO : Normally Opened, C : Common, NC : Normally Closed
When alarm is
not occurring
When alarm is
occurring
Note
If diagnosis output is enabled, I01 is fixed to de-energized operation.
Section 7.1