For the procedure to set the functions, see section 1.10, “Function Setup Guide.”

1.3 Alarms

1

2

3

4

5

6

7

8

9

10

11

12

App

Index

AND/OR Operaton of Alarm Output Relays

When multiple alarms are assigned to one alarm output relay, the condition for activating
the alarm output relay can be selected from the following:
• AND: Activated when all assigned alarms are occurring simultaneously.
• OR: Activated when any of the specified alarms is occurring.

Alarm

Channel 01

AND

Channel 02

OR

Alarm output relay

The alarm output relays assigned to AND operation are specified as follows: “I01 (first
relay) to Ixx (where xx is the relay number).”
The default setting is “no AND relay.”

Note

• If the reflash alarm is enabled, I01 to I03 are fixed to OR operation. Specifying AND

produces no effect.

• If diagnosis output is enabled, I01 is set to diagnosis output. Specifying AND produces no

effect.

Setting the AND operation: Section 7.1

Energzed/De-energzed Operaton of Alarm Output Relays

You can select whether the alarm output relay is energized or de-energized when an
alarm occurs. If de-energized is selected, the status of the alarm output relay when an
alarm occurs is the same as the status that results when the recorder is turned OFF
(including power failures). The setting applies to all alarm output relays.
The default setting is energized.

NO

Energize

De-energize

C

NC

NO

C

NC

NO

C

NC

NO

C

NC

NO

C

NC

NO

C

NC

When power is

turned OFF

NO : Normally Opened, C : Common, NC : Normally Closed

When alarm is

not occurring

When alarm is

occurring

Note

If diagnosis output is enabled, I01 is fixed to de-energized operation.

Setting the energized/de-energized operation of alarm output relays:

Section 7.1