Yokogawa µR20000 User Manual
Page 142
7-5
IM 04P02B01-01E
Setup
Operat
ons
for
Chang
ng/Add
ng
Funct
ons
(Bas
c
Sett
ng
Mode)
1
2
3
4
5
6
7
8
9
10
11
12
App
Index
7.3 Settng the Burnout Detecton Functon of
Thermocouples
This section explains the details of setting the burnout detection function of
thermocouples to channels set to 1-5V or TC input.
Basic Setting mode cannot be entered when recording is in progress or when
computation is in progress on models with the computation function (/M1 option).
Procedure
Changng the Settngs
1.
Hold down the
MENU
key for 3 seconds to enter Setting mode.
2.
Hold down the
and
keys simultaneously for 3 seconds to enter Basic
Setting mode.
3.
Press the
key or
SHIFT +
key to select
Burnout and then press the
key.
4.
Set each item and press the key.
Use the
key or
SHIFT +
key to select values.
For the procedure on how to enter values or characters, see section 4.2.
If you press the
ESC key in the middle of the operation, the settings entered up to
then are cancelled, and the display returns to a higher level menu.
5.
When the
Settng complete screen appears, do either of the following:
Press the key to set other channels.
If you are done, press the
ESC key.
Set the channel range.
The new setting takes effect.
Select the recording operation that is
carried out when a burnout is detected.
ESC/?
First channel
Last channel
01-01 Channel
Setting complete
Basic=Burnout
CH=01-01
Burnout=Off
Applyng the Changes and Returnng to Operaton Mode
Press the
key or
SHIFT +
key to select
End and then press the key. Press
the
key to select
Store and then press the key. The changes are applied, and
the screen returns to Operation mode. If you select
Abort and press the key, the
changes are discarded, and the screen returns to Operation mode. Press the
ESC key to
return to the
Basc= screen.
Explanaton
Burnout
Selects the action taken when a burnout is detected at the 1-5V input or the
thermocouple input.
Up: Records off the scale on the 100% side.
Down: Records off the scale on the 0% side.
Select Off when not using the burnout detection function.