For the procedure to set the functions, see section 1.10, “Function Setup Guide.”

1.8 Remote Control Functon (/R1 Opton)

1

2

3

4

5

6

7

8

9

10

11

12

App

Index

• Computaton Start/Stop (/M1 opton)

• Remote input signal: Rising edge signifies start; falling edge signifies stop
• Starts/stops the computation.
• If the computation is started, applying a rising edge signal produces no effect. If the

computation is stopped, applying a falling edge signal produces no effect.

• Computaton Reset (/M1 opton)

• Remote input signal: Trigger
• The computed results of computation channels are reset. This is valid only while

the computation is stopped. For all other cases, applying the remote signal
produces no effect.

• Prorty to Remote Recordng (/BT1 Opton)

• Remote input signal: Edge (rising/start or falling/stop)
• Starts/stops recording.
• When started with a remote signal (on a remote signal rise), stop per key operation or

communication is disabled.

• Swtchng Batch Comment (/BT1 Opton)

• Remote input signal: Level
• Switches between Start printout and Start printout 2, and between End printout and

End printout 2 depending on the status of the batch comment switching signal when
recording is started/stopped remotely.

• When starting/stopping by key operation, performs Start printout and End printout.

Remote Sgnal (Edge, Trgger, and Level)

The above actions are carried out on the rising or falling edge of the remote signal (edge),
the ON signal lasting at least 250 ms (trigger), or the ON/OFF signal (level).

Rising/Falling edge

Trigger

Level

Rising

Falling

250 ms or more

Operates at the

secondary chart speed

250 ms or more

For contact inputs, the remote signal rises when the contact switches from open to closed
and falls when the contact switches from closed to open. For open collector signals, the
remote signal rises when the collector signal (voltage level of the remote control terminal)
goes from high to low and falls when the collector signal goes low to high.

Assigning functions to the remote control input terminals: Section 7.18

Setting the secondary chart speed: Section 6.9