6

Part 1 Installation

If multiple controllers are to be connected on top of one another, prevent the controller above from
taking in the exhaust air from the controller below.

3. Power

Source

Provide a single-phase power source of (i) 100 to 115 or (ii) 200 to 230 VAC.

4. Noise Measures and Grounding

(1) Wiring and power source

PE on the power terminal block is used for protective grounding. Provide Class D grounding from this

terminal.

Use a grounding cable with a wire size of 1.0 mm

2

(#AWG17) or more, which should not be smaller

than the AC power cable.

To prevent noise generated in the controller from propagating to other equipment via the power line,

install an AC line noise filter.

Install the noise filter near the power connector on the X-SEL Controller.

POWE R

RB

M4

M3

M2

M1

LS4

LS 3

LS2

L S 1

PG1

B K1

B K3

TP

B K2

B K4

PG2

PG4

I/02

I/01

P G3

CODE

POWE R

RB

M4

M3

M2

M1

LS4

L S3

LS2

L S 1

P G1

B K1

B K3

TP

B K2

B K4

P G2

P G4

I/02

I/01

P G3

CODE

Airflow direction

Fan

Airflow

150 mm min.

150 mm min.

1 N

2 L

3 PE

150 mm min.

100/200-VAC power source

Noise

filter

Class D grounding
(protective grounding)