2.11 Troubleshooting

z Alarm messages, causes and remedial actions
If an alarm occurs, a corresponding simple alarm code will be indicated by the completed position number (four
bits of PM1 to PM8) in the remote I/O mode and remote I/O mode 2.
In the position/simple direct mode, this simple alarm code is output to the (n+2) channel.
In the half direct mode and full direct mode, this simple alarm code is output to the (n+6) channel.
[1] Check the generated alarm code using the monitor function of the PLC, etc., or connect the RC PC software

or teaching pendant and check the code on the status monitor screen.

[2] Look up the applicable alarm code in the alarm list provided in the operation manual for the controller.
[3] Take appropriate actions according to the explanation given for the applicable code.

For the alarm codes listed in the table below, take the specified action.

Code Error

name

ID

(*1)

RES

(*2)

Cause/action

0F2

Fieldbus module error

05

X

Cause: A fieldbus module error has been detected.
Action: Check the parameter.

0F3

Fieldbus module not

detected

04 X

Cause: The module could not be detected.
Action: Reconnect the power. If the error persists,

contact IAI.

(*1) ID

o Simple alarm code

(*2) RES

o Whether or not the alarm can be reset = O: Alarm can be set / X: Alarm cannot be reset