2. ACON-C/CG,

PCON-C/CG


46


(* In the table, ON indicates that the applicable bit is “1,” while OFF indicates that the bit is “0.”)

Signal type

Bits

Symbol

Description

Details

Current

position

32-bit data

-

32-bit signed integer indicating the current position.
The setting unit is 0.01 mm.
(Example) Reading: 000003FF

H

= 1023 (decimal)

= 10.23 mm

* If current positions are read as hexadecimals, negative values

are indicated by 2’s complements.

2.9 (3)

Command

current

32-bit data

-

32-bit integer.
The electrical current presently specified by a command is
indicated.
The setting unit is mA.
(Example) Reading: 000003FF

H

= 1023 (decimal)

= 1023 mA

2.9 (3)

Current

speed

32-bit data

-

32-bit integer.
The current speed is indicated.
The setting unit is 0.01 mm/sec.
(Example) Reading: 000003FF

H

= 1023 (decimal)

= 10.23 mm/sec

2.9 (3)

Alarm

code

16-bit data

-

16-bit integer.
If an alarm occurred, a corresponding alarm code is output.
If no alarm is present, “0” is set.
For details on alarms, refer to the operation manual for the
controller.

2.9 (3)

b15 EMGS

Emergency stop: An emergency stop is actuated when this
signal turns ON.

2.7.7 (2)

b14 PWR

Controller ready: This signal turns ON when the controller
becomes ready.

2.7.7 (1)

b13 ZONE2

Zone 2: This signal turns ON when the current position is inside
the specified zone.

2.7.7 (12)

b12 ZONE1

Zone 1: This signal turns ON when the current position is inside
the specified zone.

2.7.7 (12)

b11 PZONE

Position zone: This signal turns on when the current position is
inside the position zone.

2.7.7 (12)

ACON -

Not available (ON/OFF status is indeterminable).

-

b10

PCON LOAD

Load output judgment:
When this signal is ON, the specified load has been reached.
When the signal is OFF, the load has not been reached yet.
(For details, refer to the operation manual for the controller.)

2.7.7 (26)

ACON -

Not available (ON/OFF status is indeterminable).

-

b9

PCON TRQS

Torque level: When this signal is ON, the specified torque has
been reached. When the signal is OFF, the torque has not been
reached yet.
(For details, refer to the operation manual for the controller.)

2.7.7 (27)

b8 RMDS

Operation mode status: This signal is OFF when the current
mode is AUTO, or ON when the mode is MANU.

2.7.7 (19)

b7 GHMS

Home return in progress: This signal remains ON while home
return is in progress.

2.7.7 (6)

b6 PUSHS

Push motion in progress: This signal remains ON while
push-motion operation is in progress.

2.7.7 (25)

b5 PSFL

Load missed in push motion: This signal turns ON when the
actuator missed the load in push-motion operation.

2.7.7 (23)

b4

SV

Ready: This signal turns ON when the servo turns ON.

2.7.7 (5)

b3

ALM

Alarm: This signal turns ON when an alarm occurs.

2.7.7 (3)

b2 MOVE

Moving signal: This signal remains ON while the actuator is
moving.

2.7.7 (9)

b1 HEND

Home return complete: This signal turns ON when home return
is completed.

2.7.7 (6)

PLC in

put

Status

signal

b0 PEND

Position complete signal: This signal turns ON when positioning
is completed.

2.7.7 (10)