IAI America PCON-CFA User Manual

Page 200

background image

4. SCON-CA


194


(* In the table, ON indicates that the applicable bit is “1,” while OFF indicates that the bit is “0.”)

Address Bits

Symbol

Function

Details

b7 MOD1

4.7.11

b6 MOD0

Acceleration/deceleration mode:
Trapezoid pattern when both signals are OFF, S-motion when
MOD1 is OFF and MOD0 is ON, or primary delay filter when
MOD1 is ON and MOD0 is OFF.

4.7.11 (14)

b5 GSL1

Servo gain
parameter set
selection 1

b4 GSL0

Servo gain
parameter set
selection 0

Select the servo gain parameter set to be used.

4.7.11 (33)

b3 INC

Incremental specification:
Absolute position command when the signal is OFF, or
incremental position command when the signal is ON.

4.7.11 (24)

b2 DIR

Push direction specification:
When the signal is OFF, the direction of the position obtained by
subtracting the positioning band from the target position is used.
When the signal is ON, the direction of the position obtained by
adding the positioning band to the target position is used.

4.7.11 (22)

b1 PUSH

Push specification: Positioning operation when the signal is
OFF, or push-motion operation when the signal is ON.

4.7.11 (21)

Control

signal 1

b0 -

Not

available.

-

b15 BKRL

Forced brake release: The brake is released when this signal
turns ON.

4.7.11 (18)

b14 RMOD

Operation mode: The AUTO mode is selected when this signal is
OFF, and the MANU mode is selected when the signal is ON.

4.7.11 (19)

b13
b12
b11
b10

- Not

available.

-

b9 CLBR

Load cell calibration command: Calibration is performed when
this signal turns ON.

4.7.11 (32)

b8 JOG+

+Jog: The actuator moves in the direction opposite home when
this signal is ON.

4.7.11 (13)

b7 JOG-

-Jog: The actuator moves in the direction of home when this
signal is ON.

4.7.11 (13)

b6 JVEL

Jog-speed/inch-distance switching: The values set in parameter
No. 26, “Jog speed” and parameter No. 48, “Inch distance” are
used when this signal is OFF, and the values set in parameter
No. 47, “Jog speed 2” and parameter No. 49, “Inch distance 2”
are used when the signal is ON.

4.7.11 (14)

b5 JISL

Jog/inch switching: Jog operation is performed when this signal
is OFF, and inch operation is performed when the signal is ON.

4.7.11 (15)

b4 SON

Servo ON command: The servo turns ON when this signal turns
ON.

4.7.11 (5)

b3

RES

Reset: A reset is performed when this signal turns ON.

4.7.11 (4)

b2

STP

Pause: A pause command is issued when this signal turns ON.

4.7.11 (11)

b1 HOME

Home return: A home-return command is issued when this signal
turns ON.

4.7.11 (6)

PLC output

Control

signal 2

b0 DSTR

Positioning start: A move command is issued when this signal
turns ON.

4.7.11 (8)

GSL1

GSL0

Function

OFF

OFF

Select parameter set 0.

OFF

ON

Select parameter set 1.

ON

OFF

Select parameter set 2.

ON

ON

Select parameter set 3.