beautypg.com

2 instructions, Operating mode – Omron SYSMAC CP CP1E-N@@D@-@ User Manual

Page 97

background image

2-61

2 Instructions

CP1E CPU Unit Instructions Reference Manual(W483)

Tim

er and

Cou

nter

I

n

stru

ctio

ns

2

Operating Mode

Item

TIM/TIMX
(550)

TIMH(015)/
TIMHX(551)

TMHH(540)/
TMHHX(552)

TTIM(087)/
TTIMX(555)

TIML(542)/
TIMLX(553)

Operating mode change

PV = 0
Completion Flag = OFF

---

Power interrupt/reset

PV = 0
Completion Flag = OFF

---

Execution of CNR(545)/CNRX(547)

Binary: PV = FFFF, Completion Flag = OFF
BCD: PV = FFFF or 9999, Completion Flag = OFF

Not applicable

Operation in jumped program sec-
tion (JMP(004)-JME(005))

Operating timers continue timing.

Timer status is maintained.

Operation in interlocked program
section (IL(002)-ILC(003))

PV = SV
Completion Flag = OFF

Timer status main-
tained.

PV = SV
Completion Flag =
OFF

Forced set

Completion Flag

ON

---

PVs

Set to 0.

---

Forced reset

Completion
Flags

OFF

---

PVs

Reset to SV.

Set to 0.

---

This manual is related to the following products: