beautypg.com

Timl/timlx, Applicable program areas operands, Flags – Omron SYSMAC CP CP1E-N@@D@-@ User Manual

Page 113: 2 instructions, Operand specifications, D1: completion flag d2: pv word s: sv word

background image

2-77

2 Instructions

CP1E CPU Unit Instructions Reference Manual(W483)

Tim

er and

Cou

nter

I

n

stru

ctio

ns

2

TIML/TIMLX

TIML/TIMLX

Applicable Program Areas

Operands

Operand Specifications

Flags

Instruction

Mnemonic

Variations

Function

code

Function

LONG TIMER

TIML

---

542

TIML(542)/TIMLX(553) operates a decrementing
timer with units of 0.1s.

TIMLX

---

553

Symbol

TIML

TIMLX

BCD

Binary

Area

Step program areas

Subroutines

Interrupt tasks

Usage

OK

OK

Not allowed

Operand

Description

Data type

Size

TIML

TIMLX

D1

Completion Flag

WORD

UINT

1

D2

PV word

DWORD

UDINT

2

S

SV word

DWORD

UDINT

2

D1: Completion Flag

D2: PV Word

S: SV Word

The PV and SV can range from #00000000
to #99999999 for TIML(542) and &00000000
to &4294967294 (decimal) or #00000000 to
#FFFFFFFF (hexadecimal) for TIMLX(553).

Note S, S+1, D2 and D2+1 must be in the same

data area.

Area

Word addresses

Indirect DM addresses

Constants

CF

Pulse bits

TR bits

CIO

WR

HR

AR

T

C

DM

@DM

*DM

D1,D2

OK

OK

OK

OK

---

---

OK

OK

OK

---

---

---

---

S

OK

OK

OK

Name

Label

Operation

Error Flag

P_ER

ON if in BCD mode and D2 does not contained BCD data.

ON if in BCD mode and S does not contained BCD data.

OFF in all other cases.

TIML(542)

D1

D2

S

D1: Completion Flag

D2: PV word

S: SV word

TIMLX(553)

D1

D2

S

D1: Completion Flag

D2: PV word

S: SV word

15

D1

0

Completion Flag

Do not use.

D2

D2+1

D2

D2+1 is the leftmost 4 digits,
D2 is the rightmost 4 digits

S

S+1

S

S+1 is the leftmost 4 digits,
S is the rightmost 4 digits

This manual is related to the following products: