Timl/timlx, Applicable program areas operands, Flags – Omron SYSMAC CP CP1E-N@@D@-@ User Manual
Page 113: 2 instructions, Operand specifications, D1: completion flag d2: pv word s: sv word
2-77
2 Instructions
CP1E CPU Unit Instructions Reference Manual(W483)
Tim
er and
Cou
nter
I
n
stru
ctio
ns
2
TIML/TIMLX
TIML/TIMLX
Applicable Program Areas
Operands
Operand Specifications
Flags
Instruction
Mnemonic
Variations
Function
code
Function
LONG TIMER
TIML
---
542
TIML(542)/TIMLX(553) operates a decrementing
timer with units of 0.1s.
TIMLX
---
553
Symbol
TIML
TIMLX
BCD
Binary
Area
Step program areas
Subroutines
Interrupt tasks
Usage
OK
OK
Not allowed
Operand
Description
Data type
Size
TIML
TIMLX
D1
Completion Flag
WORD
UINT
1
D2
PV word
DWORD
UDINT
2
S
SV word
DWORD
UDINT
2
D1: Completion Flag
D2: PV Word
S: SV Word
The PV and SV can range from #00000000
to #99999999 for TIML(542) and &00000000
to &4294967294 (decimal) or #00000000 to
#FFFFFFFF (hexadecimal) for TIMLX(553).
Note S, S+1, D2 and D2+1 must be in the same
data area.
Area
Word addresses
Indirect DM addresses
Constants
CF
Pulse bits
TR bits
CIO
WR
HR
AR
T
C
DM
@DM
*DM
D1,D2
OK
OK
OK
OK
---
---
OK
OK
OK
---
---
---
---
S
OK
OK
OK
Name
Label
Operation
Error Flag
P_ER
• ON if in BCD mode and D2 does not contained BCD data.
• ON if in BCD mode and S does not contained BCD data.
• OFF in all other cases.
TIML(542)
D1
D2
S
D1: Completion Flag
D2: PV word
S: SV word
TIMLX(553)
D1
D2
S
D1: Completion Flag
D2: PV word
S: SV word
15
D1
0
Completion Flag
Do not use.
D2
D2+1
D2
D2+1 is the leftmost 4 digits,
D2 is the rightmost 4 digits
S
S+1
S
S+1 is the leftmost 4 digits,
S is the rightmost 4 digits