Scl2, Applicable program areas operands, 2 instructions – Omron SYSMAC CP CP1E-N@@D@-@ User Manual
Page 316: P1: first parameter word operand specifications
2 Instructions
2-280
CP1E CPU Unit Instructions Reference Manual(W483)
SCL2
Applicable Program Areas
Operands
P1: First Parameter Word
Operand Specifications
Instruction
Mnemonic
Variations
Function
code
Function
SCALING 2
SCL2
@SCL2
486
Converts signed binary data into signed BCD data
according to the specified linear function. An offset
can be input in defining the linear function.
Symbol
SCL2
Area
Step program areas
Subroutines
Interrupt tasks
Usage
OK
OK
OK
Operand
Description
Data type
Size
S
Source word
INT
1
P1
First parameter word
WORD
3
R
Result word
WORD
1
Note P1 to P1+2 must be in the same area.
Area
Word addresses
Indirect DM addresses
Constants
CF
Pulse bits
TR bits
CIO
WR
HR
AR
T
C
DM
@DM
*DM
S, P1, R
OK
OK
OK
OK
OK
OK
OK
OK
OK
---
---
---
---
S: Source word
P1: First parameter word
R: Result word
SCL2(486)
S
P1
R
P1
P1+1
P1+2
15
0
15
0
15
0
Offset of linear function
8000 to 7FFF (signed binary)
8000 to 7FFF (signed binary)
0000 to 9999 (BCD)