2 Instructions

2-268

CP1E CPU Unit Instructions Reference Manual(W483)

Starting PIDAT(191) with Autotuning

Interrupting Autotuning Before Completion

Autotuning can be interrupted by turning bit 15 of D209 (C+9) from ON to OFF. PID control will be
restarted with the P, I, and D constants that were in effect before autotuning was started.

At the rising edge of CIO 0.00 (OFF to ON), autotuning will be performed first if bit
15 of D209 (C+9) is ON. When autotuning is completed, the calculated P, I, and D
constants are written to C+1, C+2, and C+3. PID control is then started with the
calculated PID constants.

PIDAT

10

D200

20

0.00

S

C

D

CIO 0.00

PV

SV

MV

PID control and
autotuning start.

Calculated PID
constants are set.

AT executing

PID control

Bit 15 of D209

Time

Time

CIO 0.00

PV

SV

PID control starts.

PID control

AT executing

PID control

AT starts

AT is interrupted.

Bit 15 of D209

PID control is restarted with the
existing PID constants.

Time