beautypg.com

Applicable program areas operands, Flags, 2 instructions – Omron SYSMAC CP CP1E-N@@D@-@ User Manual

Page 410: C: control word operand specifications

background image

2 Instructions

2-374

CP1E CPU Unit Instructions Reference Manual(W483)

RXD

Applicable Program Areas

Operands

C: Control Word

Operand Specifications

Flags

Instruction

Mnemonic

Variations

Function

code

Function

RECEIVE

RXD

@RXD

235

Reads the specified number of bytes of data from
the CPU Unit’s built-in RS-232C port or the Serial
Option Board port.

Symbol

RXD

Area

Step program areas

Subroutines

Interrupt tasks

Usage

OK

OK

OK

Operand

Description

Data type

Size

D

First destination word

UINT

Variable

C

Control word

UINT

1

N

Number of bytes to store 0000 to 0100 hex (0 to 256 decimal)

UINT

1

Area

Word addresses

Indirect DM addresses

Constants

CF

Pulse bits

TR bits

CIO

WR

HR

AR

T

C

DM

@DM

*DM

D

OK

OK

OK

OK

OK

OK

OK

OK

OK

---

---

---

---

C, N

OK

Name

Label

Operation

Error Flag

P_ER

ON if no-protocol mode is not set in the PLC Setup.

ON if the value of C is not within range.

ON if the value for N is not between 0000 and 0100 hex.

OFF in all other cases.

RXD(235)

D

C

N

D: First destination word

C: Control word

N: Number of bytes to store

0000 to 0100 hex (0 to 256 decimal)

C

8

12

3

4

15

0

7

11

Byte order
0 Hex: Most significant byte to least significant byte
1 Hex: Lest significant byte to most significant byte

CS and DR signal monitoring
0: No CS and DR signal monitoring
1: CS signal monitoring
2: DR signal monitoring
3: CS and DR signal monitoring.

Always 0

Serial port specifier

1: CPU Unit’s RS-232C port

2: Serial Option Board port

This manual is related to the following products: