2 instructions, Using tpo(685) alone – Omron SYSMAC CP CP1E-N@@D@-@ User Manual

Page 311

background image

2-275

2 Instructions

CP1E CPU Unit Instructions Reference Manual(W483)

Data C

ont

ro

l I

n

stru

ctio

ns

2

TPO

Using TPO(685) Alone

When CIO 0.00 is ON, TPO(685) takes the duty ratio in D10, converts the duty ratio to a time-propor-
tional output, and outputs the pulses to bit 00 of CIO 100.

In this case, the control period is 1 s and the output limit function is enabled with a lower limit 20.00%
and an upper limit of 80.00%.

0.00

TPO

D10

D0

100.00

S

C

R

D0

D1

D2

D3

D4

D5

D6

:

:

D10

0

4

0

0

0

6

D

4

1

0

7

F

1

0

0

1

Duty ratio

Parameters

Pulse output

Duty ratio input, read initial value, and enable output limit function.

Control period = 1.00 s

Output lower limit = 20.00%

Output upper limit = 80.00%

0 to 100.00%

Do not set.

Do not set.

Do not set.

0 to 2710 hex

TPO(685) takes the duty ratio in D10, converts that duty
ratio to a time-proportional output, and outputs the pulse
output to bit 00 of CIO 100.