2-23

2 Instructions

CP1E CPU Unit Instructions Reference Manual(W483)

Seq

uen

ce Ou

tp
ut I

n

stru

ctio

ns

2

KEE

P

If a holding bit is used for R, the bit status will be retained even during a power interruption.

KEEP(011) can thus be used to program bits that will maintain status after restarting the PLC follow-
ing a power interruption. An example of this that can be used to produce a warning display following
a system shutdown for an emergency situation is shown below.

The status of I/O Area bits can be retained in the event of a power interruption by turning ON the IOM

Hold Bit and setting IOM Hold Bit Hold in the PLC Setup. In this case, I/O Area bits used in
KEEP(011) will maintain status after restarting the PLC following a power interruption, just like hold-
ing bits. Be sure to restart the PLC after changing the PLC Setup; otherwise the new settings will not
be used.

Precautions

If S and R are ON simultaneously, the reset

input takes precedence.

The set input (S) cannot be received while

R is ON.

Never use an input bit in a normally closed

condition on the reset (R) for KEEP(011)
when the input device uses an AC power
supply. The delay in shutting down the
PLC’s DC power supply (relative to the AC
power supply to the input device) can cause
the operand bit of KEEP(011) to be reset.
This situation is shown on the right.

0.02

0.03

0.04

0.05

H0.00

KEEP

H0.00

100.00

Reset input

Indicates
emergency
situation

Activates
warning
display

ON
OFF

ON
OFF

ON
OFF

Set

Reset

Status of C

ON
OFF

ON
OFF

ON
OFF

Set

Reset

Status of C

NEVER

S

R

A

KEEP

A

Input Unit