2 instructions, Differences between interlocks and jumps – Omron SYSMAC CP CP1E-N@@D@-@ User Manual
Page 73

2-37
2 Instructions
CP1E CPU Unit Instructions Reference Manual(W483)
Sequ
ence C
ontr
ol I
n
stru
ctio
ns
2
Differences between Interlocks and Jumps
The following table shows the differences between interlocks (created with IL(002)/ILC(003),
MILH(517)/MILC(519), or MILR(518)/MILC(519)) and jumps created with JMP(004)/JME(005).
Item
Treatment in IL(002)/ILC(003),
MILH(517)/MILC (519), or
MILR(518)/MILC (519)
Treatment in
JMP(004)/JME(005)
Instruction execution
Except OUT, OUT NOT, and timer
instructions, all instructions are not
executed.
No instructions are executed.
Output status in instructions
Except for outputs in OUT, OUT NOT,
and timer instructions, all outputs
retain their previous status.
All outputs retain their previous status.
Bits in OUT, OUT NOT
OFF
All outputs retain their previous status.
Status of timer instructions
(except (TTIM(087), TTIMX(555),
MTIM(543), and MTIMX(554))
Reset
Operating timers (TIM, TIMX(550),
TIMH(015), TIMHX(551), TMHH(540),
TMHHX(552) only) continue timing
because the PVs are updated even
when the timer instruction is not being
executed.