Page 307: External wiring example

background image

2-271

2 Instructions

CP1E CPU Unit Instructions Reference Manual(W483)

Data C

ont

ro

l I

n

stru

ctio

ns

2

TPO

In this case, set the same value for the PID Control instruction’s output range and the TPO(685) instruc-
tion’s manipulated variable range. For example, when the PID Control instruction’s output range and the
TPO(685) instruction’s manipulated variable range are both set to 12 bits (0000 to 0FFF hex), the duty
ratio is calculated by dividing the manipulated variable from the PID Control instruction by 0FFF hex
and TPO(685) converts that duty ratio to a time-proportional output.

External Wiring Example

Connect the Transistor Output Unit to a solid state relay (SSR) as shown in the following diagram.

Parameter Settings

Note When the output limit control function is enabled, set the lower and upper limits as follows:

0000 hex

≤ lower limit ≤ upper limit ≤ 2710 hex.

Execution

The instruction is executed while the input condition is ON.

When instruction execution starts, the output bit (R) is turned ON/OFF according to the duty ratio.

Control data

Item

Contents

Setting range

Change with

ON input

condition

Word

Bits

C

00 to 03

Manipulated
variable range

Specifies the number of input data bits.

0 hex: 8 bits

5 hex: 13 bits

1 hex: 9 bits

6 hex: 14 bits

2 hex: 10 bits

7 hex: 15 bits

3 hex: 11 bits

8 hex: 16 bits

4 hex: 12 bits

Allowed

04 to 07

Input type

Specifies whether S contains a duty ratio
or manipulated variable.

0 hex: Duty ratio

Setting range for S: 0000 to 2710 hex (0.00 to
100.00%)

1 hex: Manipulated variable

Setting range for S: 0000 to FFFF hex (0 to
65,535)
(The maximum setting depends on the MV range
set with bits 00 to 03 of C.)

Allowed

08 to 11

Input read tim-
ing

Specifies the input read timing.

0 hex: Use the beginning value of the control period

1 hex: Use lower value

2 hex: Use higher value

3 hex: Continuous adjustment

Allowed

12 to 15

Output limit
control

Specifies whether the output limit function
is enabled or disabled.

0 hex: Disabled

1 hex: Enabled (See note.)

Allowed

C+1

00 to 15

Control period

Control period
(Time period in which the ON/OFF
changes are made.)

0064 to 270F hex (1.00 to 99.99 s)

Note For example, 1.00 s is set as 0064 hex, and not

0001 hex.

Allowed

C +2

00 to 15

Output lower
limit

Specifies the lower limit when the output
limit is enabled.

0000 to 2710 hex (0 to 100.00%)

Allowed

C +3

00 to 15

Output upper
limit

Specifies the upper limit when the output
limit is enabled.

0000 to 2710 hex (0 to 100.00%)

Allowed

C+4

00 to 15

Work area

This work area is used by the system. It
cannot be used by the user.

Cannot be used.

---

C+5

00 to 15

C+6

00 to 15

COM

SSR

AC

+

Transistor Output Unit

Heater

12 to 24 VDC