beautypg.com

Related auxiliary area words and bits, Function, 2 instructions – Omron SYSMAC CP CP1E-N@@D@-@ User Manual

Page 430: Generating fatal user-defined errors

background image

2 Instructions

2-394

CP1E CPU Unit Instructions Reference Manual(W483)

Related Auxiliary Area Words and Bits

Auxiliary Area Words/Flags for User-defined Errors Only

Auxiliary Area Words/Flags for System Errors Only

Auxiliary Area Words/Flags for both User-defined and System Errors

Function

Generating Fatal User-defined Errors

When FALS(007) is executed with N set to an FALS number (1 to 511) that is not equal to the content of
A529 (the system-generated FAL/FALS number), a fatal error will be generated with that FALS number
and the following processing will be performed:

1. The FALS Error Flag (A401.06) will be turned ON. (PLC operation will stop.)

2. The error code will be written to A400. Error codes C101 to C2FF correspond to FALS numbers 0001

to 01FF (1 to 511).

Note If an error more serious than the FALS(007) instruction (one with a higher error code) has occurred, A400

will contain the more serious error’s error code.

3. The error code and the time/date that the error occurred will be written to the Error Log Area (A100

through A199).

4. The ERR Indicator on the CPU Unit will be lit.

5. If a word address has been specified in S, the ASCII message beginning at S will be registered (dis-

played on the Peripheral Device).

Note 1 If an error that is more serious (including fatal system errors) than an error registered with this instruction

occurs simultaneously, the error code of that error will be set in error code A400.

2 The end code for the message is the null character (00 hexadecimal). All 16 characters in words S to S+7

will be displayed if the null character is omitted.

3 N must between 0001 and 01FF. An error will occur and the Error Flag will be turned ON if N is outside of

the specified range.

Name

Address

Operation

FALS Error Flag

A401.06

ON when an error is generated with FALS(007).

Name

Address

Operation

System-generated FAL/FALS
number

A529

A dummy FAL/FALS number is used when a system error is generated with FALS(007). Set the same
dummy FAL/FALS number in this word (0001 to 01FF hex, 1 to 511 decimal).

Name

Address

Operation

Error Log Area

A100 to A199

The Error Log Area contains the error codes and time/date of occurrence for the most recent 20 errors,
including errors generated by FALS(007).

Error code

A400

When an error occurs its error code is stored in A400. The error codes for FALS numbers 0001 to 01FF
(1 to 511 decimal) are C101 to C2FF, respectively.

Note If two or more errors occur simultaneously, the error code of the most serious error will be stored

in A400.

FALS number

1 to 511

FALS error codes

C101 TO C2FF

FALS Error Flag ON

Error code written to A400

Error code and time/date written to Error Log Area

ERR Indicator lit

Execution of
FALS(007)
generates a
fatal error
with FALS
number N.

FALS

N

0000

This manual is related to the following products: