Scl3, Applicable program areas operands, 2 instructions – Omron SYSMAC CP CP1E-N@@D@-@ User Manual

Page 320: P1: first parameter word

background image

2 Instructions

2-284

CP1E CPU Unit Instructions Reference Manual(W483)

SCL3

Applicable Program Areas

Operands

P1: First Parameter Word

Instruction

Mnemonic

Variations

Function

code

Function

SCALING 3

SCL3

@SCL3

487

Converts signed BCD data into signed binary data
according to the specified linear function. An offset
can be input in defining the linear function.

Symbol

SCL3

Area

Step program areas

Subroutines

Interrupt tasks

Usage

OK

OK

OK

Operand

Description

Data type

Size

S

Source word

WORD

1

P1

First parameter word

WORD

5

R

Result word

INT

1

Note P1 to P1+4 must be in the same area.

S: Source word

P1: First parameter word

R: Result word

SCL3(487)

S

P1

R

P1

P1+1

P1+2

P1+3

P1+4

15

0

15

0

15

0

15

0

15

0

∆X

∆Y

Offset of linear function
8000 to 7FFF (signed binary)

0001 to 9999 (BCD)

8000 to 7FFF (signed binary)

Maximum conversion
8000 to 7FFF (signed binary)

Minimum conversion
8000 to 7FFF (signed binary)