2 Instructions

2-20

CP1E CPU Unit Instructions Reference Manual(W483)

TR

Function

TR bits are used to temporarily retain the ON/OFF status of execution conditions in a program when
programming in mnemonic code. They are not used when programming directly in ladder program form
because the processing is automatically executed by the Peripheral Device. The following diagram
shows a simple application using two TR bits.

Instruction

Mnemonic

Variations

Function

code

Function

TR Bits

TR

---

---

TR bits are used to temporarily retain the ON/OFF
status of execution conditions in a program when
programming in mnemonic code.

Using TR0 to TR15

TR0 to TR15 are used only with LOAD and

OUTPUT instructions.

There are no restrictions on the order in

which the bit addresses are used.

Sometimes it is possible to simplify a pro-

gram by rewriting it so that TR bits are not
required. The following diagram shows one
case in which a TR bit is unnecessary and
one in which a TR bit is required.

In instruction block (1), the ON/OFF status at
point A is the same as for output CIO 100.00,
so AND 0.01 and OUT 100.01 can be coded
without requiring a TR bit. In instruction block
(2), the status of the branching point and that
of output CIO 100.02 are not necessarily the
same, so a TR bit must be used. In this case,
the number of steps in the program could be
reduced by using instruction block (1) in place
of instruction block (2).

LD 0.00

OUT

Coding

TR0

AND 0.01

OUT TR1

AND 0.02

OUT 100.00

LD TR1

AND 0.03

OUT 100.01

LD TR0

AND 0.04

OUT 100.02

LD TR0

AND NOT

100.00

OUT 100.03

Relay Address

TR0 to TR15

Temporary Relay

Instruction

Operands

0.00

0.01

0.02

0.03

0.04

0.05

100.00

100.01

100.02

100.03

TR0

TR1

A

0.00

0.01

0.02

0.03

(2)

100.00

100.01

100.02

100.03

TR0

(1)