Applicable program areas operands, 2 instructions, P1: first parameter word operand specifications – Omron SYSMAC CP CP1E-N@@D@-@ User Manual
Page 312
2 Instructions
2-276
CP1E CPU Unit Instructions Reference Manual(W483)
SCL
Applicable Program Areas
Operands
P1: First Parameter Word
Operand Specifications
Instruction
Mnemonic
Variations
Function
code
Function
SCALING
SCL
@SCL
194
Converts unsigned binary data into unsigned BCD
data according to the specified linear function.
Symbol
SCL
Area
Step program areas
Subroutines
Interrupt tasks
Usage
OK
OK
OK
Operand
Description
Data type
Size
S
Source word
UINT
1
P1
First parameter word
LWORD
4
R
Result word
WORD
1
Note P1 to P1+3 must be in the same area.
Area
Word addresses
Indirect DM addresses
Constants
CF
Pulse bits
TR bits
CIO
WR
HR
AR
T
C
DM
@DM
*DM
S, P1, R
OK
OK
OK
OK
OK
OK
OK
OK
OK
---
---
---
---
S: Source word
P1: First parameter word
R: Result word
SCL(194)
S
P1
R
P1
P1+1
P1+2
P1+3
15
0
15
0
15
0
15
0
Scaled value for point A (Ar)
0000 to 9999 (4-digit BCD)
Unscaled value for point A (As)
0000 to FFFF (binary)
Scaled value for point B (Br)
0000 to 9999 (4-digit BCD)
Unscaled value for point B (Bs)
0000 to FFFF (binary)