2 Instructions

2-40

CP1E CPU Unit Instructions Reference Manual(W483)

IL/ILC

Applicable Program Areas

Flags

There are no flags affected by this instruction.

Function

When the execution condition for IL(002) is OFF, the outputs for all instructions between IL(002) and
ILC(003) are interlocked. When the execution condition for IL(002) is ON, the instructions between
IL(002) and ILC(003) are executed normally.

The following table shows the treatment of various outputs in an interlocked section between IL(002)
and ILC(003).

Note Bits and words in all other instructions including TTIM(087), TTIMX(555), SET, RSET, CNT, CNTX(546),

CNTR(012), CNTRX(548), SFT, and KEEP(011) retain their previous status.

Instruction

Mnemonic

Variations

Function

code

Function

INTERLOCK

IL

---

002

Interlocks all outputs between IL(002) and
ILC(003) when the execution condition for IL(002)
is OFF.

INTERLOCK CLEAR

ILC

---

003

Indicates the end of the interlock range.

Symbol

IL

ILC

Area

Step program areas

Subroutines

Interrupt tasks

Usage

Not allowed

OK

OK

Instruction

Treatment

Bits specified in OUT, OUT NOT

OFF

TIM, TIMX(550), TIMH(015), TIMHX(551), TMHH(540),
TMHHX(552), TIML(542), and TIMXL(553)

Completion Flag

OFF (reset)

PV

Time set value (reset)

Bits/words specified in all other instructions (See note.)

Retain previous status.

IL(002)

ILC(003)

IL

ILC

Execution
condition

Execution
condition ON

Execution
condition OFF

Interlocked section
of the program

Normal Outputs
execution interlocked.