Cnt/cntx, Applicable program areas operands, Flags – Omron SYSMAC CP CP1E-N@@D@-@ User Manual
Page 116: 2 instructions, N: counter number, S: set value, Operand specifications
2 Instructions
2-80
CP1E CPU Unit Instructions Reference Manual(W483)
CNT/CNTX
Applicable Program Areas
Operands
N: Counter Number
The counter number must be between 0000 and 0255 (decimal).
S: Set Value
CNT (BCD): #0000 to #9999
CNTX (Binary): &0 to &65535 (decimal) or #0000 to #FFFF (hex)
Operand Specifications
Flags
Instruction
Mnemonic
Variations
Function
code
Function
COUNTER
CNT/CNTX
---
546
CNT/CNTX(546) operates a decrementing
counter.
Symbol
CNT
CNTX
BCD
Binary
Area
Step program areas
Subroutines
Interrupt tasks
Usage
OK
OK
OK
Operand
Description
Data type
Size
CNT
CNTX
N
Counter Number
COUNTER
COUNTER
1
S
Set Value
WORD
UINT
1
Area
Word addresses
Indirect DM addresses
Constants
CF
Pulse bits
TR bits
CIO
WR
HR
AR
T
C
DM
@DM
*DM
N
---
---
---
---
---
OK
---
---
---
---
---
---
---
S
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
Name
Label
Operation
Error Flag
P_ER
• ON if in BCD mode and S does not contain BCD data.
• OFF in all other cases.
CNT
N
S
Count input
Reset input
N: Counter number
S: Set value
CNTX(546)
N
S
Count input
Reset input
N: Counter number
S: Set value