Sped, Applicable program areas operands, 2 instructions – Omron SYSMAC CP CP1E-N@@D@-@ User Manual
Page 355: P: port specifier operand specifications, M: output mode f: first pulse frequency word
2-319
2 Instructions
CP1E CPU Unit Instructions Reference Manual(W483)
High-speed
Counter/Pulse
Ou
tp
ut I
n
stru
ctio
ns
2
SPE
D
SPED
Applicable Program Areas
Operands
P: Port specifier
Operand Specifications
Instruction
Mnemonic
Variations
Function
code
Function
SPEED OUTPUT
SPED
@SPED
885
SPED(885) is used to set the output pulse frequency for a specific
port and start pulse output without acceleration or deceleration.
Symbol
SPED
Area
Step program areas
Subroutines
Interrupt tasks
Usage
OK
OK
OK
Operand
Description
Data type
Size
P
Port specifier
UINT
1
M
Output mode
WORD
1
F
First pulse frequency word
UDINT
2
P
Port
0000 hex
Pulse output 0
0001 hex
Pulse output 1
M: Output mode
F: First pulse frequency word
Specify the pulse frequency in Hz.
Area
Word addresses
Indirect DM addresses
Constants
CF
Pulse bits
TR bits
CIO
WR
HR
AR
T
C
DM
@DM
*DM
P, M
---
---
---
---
---
---
---
---
---
OK
---
---
---
F
OK
OK
OK
OK
OK
OK
OK
OK
OK
---
F: First pulse frequency word
SPED(855)
P
M
F
P: Port specifier
M: Output mode
0
3
4
7
8
11
12
15
M
Mode
0 hex: Continuous
1 hex: Independent
Direction
0 hex: CW
1 hex: CCW
Pulse output method
1 hex: Pulse + direction
Always 0 hex.
F
F+1
0
15
Lower word of target frequency
Upper word of target frequency
0 to 100,000 Hz
(0000 0000 to 0001 86A0 hex)