Applicable Program Areas

Operands

P: Port Specifier

M: Output Mode

Instruction

Mnemonic

Variations

Function

code

Function

PULSE OUTPUT

PLS2

@PLS2

887

PLS2(887) outputs a specified number of pulses
to the specified port. Pulse output starts at a spec-
ified startup frequency, accelerates to the target
frequency at a specified acceleration rate, decel-
erates at the specified deceleration rate, and stops
at approximately the same frequency as the star-
tup frequency.

Symbol

PLS2

Area

Step program areas

Subroutines

Interrupt tasks

Usage

OK

OK

OK

Operand

Description

Data type

Size

P

Port specifier

---

1

M

Output mode

---

1

S

First word of settings table

WORD

6

F

First word of starting frequency

UDINT

2

P

Port

0000 hex

Pulse output 0

0001 hex

Pulse output 1

P: Port specifier

M: Output mode

S: First word of settings table

F: First word of starting frequency

PLS2(887)

P

M

S

F

0

3

4

7

8

11

12

15

M

Relative/absolute specifier
0 hex: Relative pulses
1 hex: Absolute pulses

Direction
0 hex: CW
1 hex: CCW

Pulse output method
1 hex: Pulse + direction

Always 0 hex.