beautypg.com

Applicable program areas operands, 2 instructions – Omron SYSMAC CP CP1E-N@@D@-@ User Manual

Page 339

background image

2-303

2 Instructions

CP1E CPU Unit Instructions Reference Manual(W483)

I

n

terru

pt C

ont

ro

l I

n

stru

ctio

ns

2

CLI

CLI

Applicable Program Areas

Operands

(1) Clearing/Retaining an I/O Interrupt Task’s Recorded Interrupt Inputs

(2) Setting the Time to the First Scheduled Interrupts

Instruction

Mnemonic

Variations

Function

code

Function

CLEAR INTERRUPT

CLI

@CLI

691

Clears/retains recorded interrupt inputs, sets the
time to the first scheduled interrupt for scheduled
interrupt tasks.

Symbol

CLI

Area

Step program areas

Subroutines

Interrupt tasks

Usage

OK

OK

OK

Operand

Description

Data type

Size

N

Interrupt number

---

1

C

Control data

UINT

1

Operand

Contents

N

Interrupt Input No.

102: Interrupt input 2 (interrupt task 2)

103: Interrupt input 3 (interrupt task 3)

104: Interrupt input 4 (interrupt task 4)

105: Interrupt input 5 (interrupt task 5)

106: Interrupt input 6 (interrupt task 6) (Cannot be used in CP1E-E10D - )

107: Interrupt input 7 (interrupt task 7) (Cannot be used in CP1E-E10D - )

C

Recorded Interrupt

0000 hex: Retain the recorded interrupt.

0001 hex: Clear the recorded interrupt.

Operand

Contents

N

Scheduled Interrupt No.

4: Interrupt task 0 (interrupt task 1)

C

Scheduled interrupt time units

(Set in the PLC Setup.)

Scheduled interrupt set time

0.1 ms

10 to 9,999 decimal (000A to 270F hex):
Sets time to first interrupt between 1.0 and 999.9 ms.

N: Interrupt number

C: Control data

CLI(691)

N

C

This manual is related to the following products: