Puls, Applicable program areas operands, 2 instructions – Omron SYSMAC CP CP1E-N@@D@-@ User Manual
Page 359: Operand specifications

2-323
2 Instructions
CP1E CPU Unit Instructions Reference Manual(W483)
High-speed
Counter/Pulse
Ou
tp
ut I
n
stru
ctio
ns
2
PULS
PULS
Applicable Program Areas
Operands
P: Port specifier
T: Pulse type
N and N+1: Number of pulses
• The actual number of movement pulses that will be output are as follows:
For relative pulse output, the number of movement pulses = the set number of pulses.
For absolute pulse output, the number of movement pulses = the set number of pulses - the PV.
Operand Specifications
Instruction
Mnemonic
Variations
Function
code
Function
SET PULSES
PULS
@PULS
886
PULS(886) is used to set the pulse output amount (number of out-
put pulses).
Symbol
PULS
Area
Step program areas
Subroutines
Interrupt tasks
Usage
OK
OK
OK
Operand
Description
Data type
Size
P
Port specifier
---
1
T
Pulse type
---
1
N
Number of pulses
DINT
2
P
Port
0000 hex
Pulse output 0
0001 hex
Pulse output 1
T
Pulse type
0000 hex
Relative
0001 hex
Absolute
Area
Word addresses
Indirect DM addresses
Constants
CF
Pulse bits
TR bits
CIO
WR
HR
AR
T
C
DM
@DM
*DM
P, T
---
---
---
---
---
---
---
---
---
OK
---
---
---
N
OK
OK
OK
OK
OK
OK
OK
OK
OK
N: Number of pulses
PULS(886)
P
T
N
P: Port specifier
T: Pulse type
N
N+1
0
15
Lower word with number of pulses
Upper word with number of pulses