2 Instructions

2-106

CP1E CPU Unit Instructions Reference Manual(W483)

Function

ZCP

ZCP(088) compares the 16-bit signed binary data in CD with the range defined by LL and UL and out-
puts the result to the Greater Than, Equals, and Less Than Flags in the Auxiliary Area. (The Less Than
or Equal, Greater Than or Equal, and Not Equal Flags are left unchanged.)

When CD > UL as shown below, the > flag turns ON.
When LL

≤ CD ≤ UL, the = flag turns ON. When CD < LL, the < flag turns ON.

ZCPL

ZCPL(116) compares the 32-bit signed binary data in CD+1, CD with the range defined by LL+1, LL
and UL+1, UL and outputs the result to the Greater Than, Equals, and Less Than Flags in the Auxiliary
Area. (The Less Than or Equal, Greater Than or Equal, and Not Equal Flags are left unchanged.)

When CD+1,CD > UL+1,UL as shown below, the > flag turns ON.
When LL+1,LL

≤ CD+1, CD ≤ UL+1, UL, the = flag turns ON.

When CD+1, CD < LL+1, LL, the < flag turns ON.

Precautions

When ZCP(088)/ZCPL(116) is executed, the result is reflected in the Arithmetic Flags. Control the

desired output or right-hand instruction with a branch from the same input condition that controls
ZCP(088)/ZCPL(116), as shown in the following diagram.

ZCP(088)Result

Flag status

>

=

<

CD > UL

ON

OFF

OFF

CD = UL

OFF

ON

LL < CD < UL

CD = LL

CD < LL

OFF

ON

ZCPL(116)Result

Flag status

>

=

<

CD+1, CD > UL+1, UL

ON

OFF

OFF

CD+1, CD = UL+1, UL

OFF

ON

LL+1, LL < CD+1, CD <
UL+1, UL

CD+1, CD = LL+1, LL

CD+1, CD < LL+1, LL

OFF

ON

A

ZCP

CD

LL

UL

Arithmetic Flag
(Example: Equal Flag)

In this case, the Equals Flag and output A will be

turned ON when LL

CD

UL.