Timh/timhx, Applicable program areas operands, Flags – Omron SYSMAC CP CP1E-N@@D@-@ User Manual
Page 105: 2 instructions, N: timer number, S: set value, Operand specifications
![background image](/manuals/204951/105/background.png)
2-69
2 Instructions
CP1E CPU Unit Instructions Reference Manual(W483)
Tim
er and
Cou
nter
I
n
stru
ctio
ns
2
TIMH/
T
IMHX
TIMH/TIMHX
Applicable Program Areas
Operands
N: Timer Number
The timer number must be between 0000 and 0255 (decimal).
S: Set Value
TIMH (BCD): #0000 to #9999
TIMHX (Binary): &0 to &65535 (decimal) or #0000 to #FFFF (hex)
Operand Specifications
Flags
Instruction
Mnemonic
Variations
Function
code
Function
TEN-MS TIMER
TIMH
---
015
TIMH(015)/TIMHX(551) operates a decrementing
timer with units of 10-ms.
TIMHX
---
551
Symbol
TIMH
TIMHX
BCD
Binary
Area
Step program areas
Subroutines
Interrupt tasks
Usage
OK
OK
Not allowed
Operand
Description
Data type
Size
TIMH
TIMHX
N
Timer Number
TIMER
TIMER
1
S
Set Value
WORD
UINT
1
Area
Word addresses
Indirect DM addresses
Constants
CF
Pulse bits
TR bits
CIO
WR
HR
AR
T
C
DM
@DM
*DM
N
---
---
---
---
OK
---
---
---
---
---
---
---
---
S
OK
OK
OK
OK
OK
OK
OK
OK
OK
Name
Label
Operation
Error Flag
ER
• ON if in BCD mode and S does not contain BCD data.
• OFF in all other cases.
TIMH(015)
N
S
S: Set value
N: Timer number
TIMHX(551)
N
S
S: Set value
N: Timer number