Or/or not, Applicable program areas operands, Flags – Omron SYSMAC CP CP1E-N@@D@-@ User Manual
Page 47: Function, 2 instructions, Operand specifications, Or not

2-11
2 Instructions
CP1E CPU Unit Instructions Reference Manual(W483)
Seq
uen
ce Inp
u
t I
n
stru
ctio
ns
2
OR
/OR
NO
T
OR/OR NOT
Applicable Program Areas
Operands
Operand Specifications
Flags
There are no flags affected by this instruction.
Function
Instruction
Mnemonic
Variations
Function
code
Function
OR
OR
@OR, %OR,
!OR, !@OR,
!%OR
---
Takes a logical OR of the ON/OFF status of the
specified operand bit and the current execution
condition.
OR NOT
OR NOT
@OR NOT, %OR
NOT, !OR NOT,
!@OR NOT,
!%OR NOT
---
Reverses the status of the specified bit and takes
a logical OR with the current execution condition.
Symbol
OR
OR NOT
Area
Step program areas
Subroutines
Interrupt tasks
Usage
OK
OK
OK
Operand
Description
Data type
Size
---
---
BOOL
---
Area
Word addresses
Indirect DM addresses
Constants
CF
Pulse bits
TR bits
CIO
WR
HR
AR
T
C
DM
@DM
*DM
OR
OK
OK
OK
OK
OK
OK
---
---
---
---
OK
OK
---
OR NOT
OR
OR is used for a normally open bit connected in parallel. A normally open bit is configured to form a log-
ical OR with a logic block beginning with a LOAD or LOAD NOT instruction (connected to the bus bar or
at the beginning of the logic block). If there is no immediate refreshing specification, the specified bit in
I/O memory is read. If there is an immediate refreshing specification, the status of the CPU Unit’s built-
in input terminal is read.
OR NOT
OR NOT is used for a normally closed bit connected in parallel. A normally closed bit is configured to
form a logical OR with a logic block beginning with a LOAD or LOAD NOT instruction (connected to the
bus bar or at the beginning of the logic block). If there is no immediate refreshing specification, the
specified bit in I/O memory is read. If there is an immediate refreshing specification, the status of the
CPU Unit’s built-in input terminal is read.
Bus bar
Bus bar